Environmental Considerations
Freeze Protection
Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes
the units subject to low ambient temperatures. The Logicool InRak must have a minimum of 20% glycol as standard.
Units with supply water temperatures below +5°C
Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be
exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
Glycol of an appropriate concentration
(1)
must be used within the system to ensure adequate freeze protection.
Please ensure that the concentration is capable of protection to at least 3°C lower than ambient.
Water/glycol solution should be constantly circulated through all waterside pipework and coils to avoid static water from
freezing.
Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C of the
solution freeze point
(1)
(i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).
Additional trace heating is provided for interconnecting pipework.
(1)
Refer to your glycol supplier for details.
Environmental Policy
It is our policy to:
• Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
• Train personnel in sound environmental practices.
• Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
• Manufacture products in a responsible manner with minimum impact on the environment.
• Reduce our use of chemicals and minimise their release to the environment.
• Measure, control and verify environmental performance through internal and external audits.
• Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
Electromagnetic Compatibility Directive (EMC)
2014/30/EU
Low Voltage Directive (LVD)
2014/35/EU
Machinery Directive (MD)
89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED)
97/23/EC
Article
13
of
2014/68/EU
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.
Airedale Ltd endeavours to ensure that the information in this document is correct and fairly stated, but none of the
statements are to be relied upon as a statement or representation of fact. Airedale Ltd does not accept liability for any
error or omission, or for any reliance placed on the information contained in this document. The development of Airedale
products and services is continuous and the information in this document may not be up to date. It is important to check
the current position with Airedale Ltd at the address stated. This document is not part of a contract or licence unless
expressly agreed. No part of this document may be reproduced or transmitted in any form or by any means, electronic
or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other
than the purchaser’s personal use, without the express written permission of Airedale Ltd.
© 2016 Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK.