Technical - Direct Expansion
Electrical Data - Tandem Compressor (X2)
LIR6042U-X240-0
LIR6042U-X250-0
Standard Condenser Match -
CR65
CR80
Unit Data Cooling only
(1)
Nominal Run Amps
A
27.9
29.4
Maximum Start Amps
A
89.3
89.3
Recommended Mains Fuse Size
(4)
A
50
50
Max Mains Incoming Cable Size
(5)
mm²
16
16
Mains Supply 50Hz (-0)
V
400V / 3PH + N / 50Hz
Mains Supply 60Hz (-1)
V
380V / 3PH + N / 60Hz
Control Circuit
VAC
24
Evaporator Fan - Motor - Per Fan
Motor Type
EC
EC
Quantity x Motor Size
(2)
kW
4 x 0.5
4 x 0.5
Full Load Amps
A
2.2
2.2
Locked Rotor Amps
A
N/A
N/A
Compressor 1
(3)
Motor Size
kW
5.25
5.25
Nominal Run Amps
A
18.8
18.8
Max Run Amps
A
24.9
24.9
Type of Start
Soft Start
Soft Start
Compressor 2
(3)
Motor Size
kW
4.28
4.28
Nominal Run Amps
A
6.2
6.2
Locked Rotor Amps
A
60.0
60.0
Type of Start
Direct On Line
Direct On Line
Standard Condenser Match – AC Motor
Per Fan
Quantity x Motor Size (50Hz Supply)
kW
2 x 0.6
3 x 0.6
Full Load Amps (50Hz Supply)
A
2.6
2.6
Quantity x Motor Size (60Hz Supply)
kW
2 x 0.5
3 x 0.5
Full Load Amps (60Hz Supply)
A
2.2
2.2
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
Variable
Variable
Number of Elements
3
3
Rating (Total)
kW
10.5
10.5
Current Per Phase (50Hz Supply)
A
15.2
15.2
Current Per Phase (60Hz Supply)
A
16.0
16.0
Standard Condenser Match - EC Motor-
Per Fan
Mains Supply 50Hz (-0)
V
230V / 1PH + N / 50Hz
Mains Supply 60Hz (-1)
V
220V / 1PH + N / 60Hz
Quantity x Motor Size (50Hz Supply)
kW
2 x 0.72
3 x 0.72
Full Load Amps (50Hz Supply)
A
3.2
3.2
Quantity x Motor Size (60Hz Supply)
kW
2 x 0.77
3 x 0.77
Full Load Amps (60Hz Supply)
A
3.3
3.3
SCAF Condenser Match - Motor - Per
Fan
Quantity x Motor Size (50Hz Supply)
kW
2 x 1.4
3 x 1.4
Full Load Amps (50Hz Supply)
A
6.0
6.0
Quantity x Motor Size (60Hz Supply)
kW
2 x 1.75
3 x 1.75
Full Load Amps (60Hz Supply)
A
7.8
7.8
IT Cooling
LogiCool InRak™
31
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Te
ch
nic
al
DX
(1) Values given for unit variants at 11°C evaporating and 46°C condensing.
(2) Stated motor power is based on maximum electrical power absorbed.
(3) Values are per compressor.
(4) Values may change based on additional selections (i.e. Heating).
(5) Values based on Fuse size., May change based on unit selections.