Technical - Direct Expansion
Performance Data - Tandem Compressor (X2)
Max EER (X2)
Ambient (°C)
Unit
Air On DB / RH
25
30
35
40
46
LIR6042U-X240-0
25°C / 42%
Gross Total Cooling (kW)
14.94
14.94
14.82
14.24
13.80
Power Input (kW)
3.22
3.22
3.30
3.70
4.34
EER
4.64
4.64
4.49
3.85
3.18
30°C / 32%
Gross Total Cooling (kW)
21.97
21.97
21.57
20.79
21.26
Power Input (kW)
4.39
4.39
4.67
5.20
6.26
EER
5.00
5.00
4.62
4.00
3.40
35°C / 24%
Gross Total Cooling (kW)
30.41
30.41
24.29
26.00
25.13
Power Input (kW)
5.61
5.61
4.69
5.63
6.30
EER
5.42
5.42
5.18
4.62
3.99
40°C / 18%
Gross Total Cooling (kW)
37.61
38.79
33.29
32.29
23.14
Power Input (kW)
6.63
7.05
6.33
7.15
5.79
EER
5.68
5.50
5.26
4.52
4.00
LIR6042U-X250-0
25°C / 42%
Gross Total Cooling (kW)
18.38
18.38
18.21
17.53
17.05
Power Input (kW)
4.30
4.30
4.42
4.92
5.69
EER
4.27
4.27
4.12
3.56
2.99
30°C / 32%
Gross Total Cooling (kW)
27.06
27.06
26.49
25.43
24.06
Power Input (kW)
5.66
5.66
6.07
6.82
7.79
EER
4.78
4.78
4.36
3.73
3.09
35°C / 24%
Gross Total Cooling (kW)
30.41
30.41
30.90
26.16
25.29
Power Input (kW)
5.56
5.56
6.25
5.45
6.13
EER
5.47
5.47
4.94
4.80
4.13
40°C / 18%
Gross Total Cooling (kW)
37.61
37.61
33.57
32.58
23.30
Power Input (kW)
6.58
6.58
6.05
6.86
5.64
EER
5.72
5.72
5.55
4.75
4.12
LogiCool InRak™
IT Cooling
26 InRak™ Technical Manual 7462807 V1.11.0_04_2016
Te
ch
ni
ca
l
DX
Max EER data is based on a part load condition (i.e. required duty of 50% of the maximum achievable duty of the unit).
Unit duty based on a SHR = 1.0
Performance data is based upon a unit with no filtration.