Technical - Direct Expansion
Performance Data - Single Compressor (X1)
Max EER (X1)
Ambient (°C)
Unit
Air On DB / RH
25
30
35
40
46
LIR6042U-X123-0
25°C / 42%
Gross Total Cooling (kW)
10.85
10.85
10.97
10.52
13.66
Power Input (kW)
2.15
2.15
2.27
2.58
4.43
EER
5.05
5.05
4.83
4.08
3.08
30°C / 32%
Gross Total Cooling (kW)
17.17
17.17
17.59
16.92
16.05
Power Input (kW)
3.16
3.16
3.52
3.94
4.46
EER
5.42
5.42
4.98
4.28
3.59
35°C / 24%
Gross Total Cooling (kW)
17.89
17.89
18.56
19.43
18.24
Power Input (kW)
3.06
3.06
3.36
3.97
4.43
EER
5.85
5.85
5.52
4.89
4.12
40°C / 18%
Gross Total Cooling (kW)
23.29
24.70
26.78
20.34
19.64
Power Input (kW)
4.15
4.20
4.92
3.81
4.34
EER
5.61
5.88
5.44
5.34
4.53
LIR6042U-X130-0
25°C / 42%
Gross Total Cooling (kW)
15.02
15.02
14.75
14.16
13.41
Power Input (kW)
3.27
3.27
3.46
3.87
4.38
EER
4.59
4.59
4.26
3.67
3.07
30°C / 32%
Gross Total Cooling (kW)
17.17
22.81
17.26
16.63
15.81
Power Input (kW)
3.16
4.56
3.47
3.89
4.41
EER
5.43
5.00
4.97
4.28
3.59
35°C / 24%
Gross Total Cooling (kW)
23.21
23.21
18.56
19.09
18.24
Power Input (kW)
4.23
4.23
3.35
3.91
4.44
EER
5.49
5.49
5.54
4.88
4.12
40°C / 18%
Gross Total Cooling (kW)
23.29
24.70
26.78
20.34
19.64
Power Input (kW)
4.14
4.19
4.95
3.80
4.33
EER
5.63
5.89
5.41
5.35
4.54
IT Cooling
LogiCool InRak™
25
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Te
ch
nic
al
DX
All the performance data is based on a SHR of 1.0.
Max EER data is based on a part load condition (i.e. required duty of 50% of the maximum achievable duty of the unit).
Performance data is based upon a unit with no filtration.