8
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Capacity Range Cooling Only Unit
Model No.
Nominal Cooling
Capacity (kW)
Nominal Unit Input
Power (kW)
EER
Dimensions
(H x W x L) mm
CUR092V16-1CO-0
13.8
4.1
3.37
1750 x 764 x 922
CUR092V20-1CO-0
20.3
6.2
3.26
1750 x 764 x 922
CUR092V25-1CO-0
26.0
8.4
3.10
1750 x 764 x 922
CUR092V29-1CO-0
28.6
9.5
3.01
1750 x 764 x 922
CUR122V35-1CO-0
38.8
12.5
3.10
1750 x 764 x 1222
CUR122V40-1CO-0
43.4
14.5
3.00
1750 x 764 x 1222
CUR092V16-VCO-0
15.6
4.5
3.48
1750 x 764 x 922
CUR092V20-VCO-0
20.3
6.2
3.27
1750 x 764 x 922
CUR092V25-VCO-0
24.8
7.6
3.26
1750 x 764 x 922
CUR092V29-VCO-0
28.4
9.2
3.08
1750 x 764 x 922
CUR122V35-VCO-0
37.1
12.0
3.09
1750 x 764 x 1222
CUR122V40-VCO-0
42.6
14.3
2.98
1750 x 764 x 1222
In cooling, 7°C evaporating, 35°C ambient (standard AC axial fan at maximum speed)
In heating, 50°C condensing, 5°C ambient (standard AC axial fan at maximum speed)
Input power includes compressor and fan