BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Electrical Data - Heat Pump Modulating Capacities
CUR092V16-VHP-0
CUR092V20-VHP-0
CUR092V25-VHP-0
Unit Data
(1)
Nominal Run Amps
A
11
15
17
Maximum Start Amps
A
67
104
114
Recommended Mains Fuse Size
A
16
25
25
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Condenser Fan - Motor - Per Fan
Motor Type
AC
AC
AC
1~
1~
1~
Quantity x Motor Size
kW
1 x 0.6
1 x 0.6
1 x 0.6
Full Load Amps
A
2.6
2.6
2.6
Locked Rotor Amps
A
9
9
9
Compressor
Motor Size
kW
5
7
8
Nominal Run Amps
A
9
12
15
Locked Rotor Amps
A
64
101
111
Type of Start
Direct On Line
OPTIONAL EXTRAS
Electronic Soft-start
Nominal Run Amps
A
11
15
17
Maximum Start Amps
A
41
63
69
Recommended Mains Fuse Size
A
16
25
25
Power Factor Correction
Nominal Run Amps
A
Maximum Start Amps
A
N/A
Recommended Mains Fuse Size
A
Compressor Nominal Run Amps
A
First upgrade EC Motor - Per Fan
1~
1~
1~
Quantity x Motor Size
kW
1 x 0.73
1 x 0.73
1 x 0.73
Full Load Amps
A
3.3
3.3
3.3
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade SCAF - Per Fan
1~
1~
1~
Quantity x Motor Size
kW
1 x 1.4
1 x 1.4
1 x 1.4
Full Load Amps
A
6.0
6.0
6.0
Locked Rotor Amps
A
18
18
18
(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.