49
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Electrical Data Cooling Only Variable Capacities
CUR092V29-VCO-0
CUR122V35-VCO-0
CUR122V40-VCO-0
Unit Data
(1)
Nominal Run Amps
A
19
27
32
Maximum Start Amps
A
121
145
178
Recommended Mains Fuse Size
A
32
40
50
Max Mains Incoming Cable Size
mm²
35
35
35
Mains Supply
V
400V / 3PH + N / 50Hz
Control circuit
VAC
24
24
24
Condenser Fan - Motor - Per Fan
Motor Type
AC
AC
AC
1~
3~
3~
Quantity x Motor Size
kW
1 x 0.6
1 x 1.97
1 x 1.97
Full Load Amps
A
2.6
3.4
3.4
Locked Rotor Amps
A
9.2
11.9
11.9
Compressor
Motor Size
kW
9
12
14
Nominal Run Amps
A
17
21
26
Locked Rotor Amps
A
118
140
173
Type of Start
Direct On Line
OPTIONAL EXTRAS
Electronic Soft-start
Nominal Run Amps
A
19
27
32
Maximum Start Amps
A
73
89
109
Recommended Mains Fuse Size
A
32
40
50
Power Factor Correction
Nominal Run Amps
A
Maximum Start Amps
A
N/A
Recommended Mains Fuse Size
A
Compressor Nominal Run Amps
A
First upgrade EC Motor - Per Fan
1~
3~
3~
Quantity x Motor Size
kW
1 x 0.73
1 x 1.85
1 x 1.85
Full Load Amps
A
3.3
2..85
2..85
Locked Rotor Amps
A
N/A
N/A
N/A
Second upgrade SCAF - Per Fan
1~
N/A
N/A
Quantity x Motor Size
kW
1 x 1.4
N/A
N/A
Full Load Amps
A
6.0
N/A
N/A
Locked Rotor Amps
A
18
N/A
N/A
(1) Based upon ARI conditions, Evaporating at 7°C, Condensing at 54.4°C.
CUR092V29-VCO-0 - CUR122V40-VCO-0
Condensing Unit
BluCube™
Te