73
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016
Addressing the pCO Controller
The address of the controller can be configured by setting the display keypad to address 0 (zero).
To change the address of the pCO controller, press and hold the + buttons together and switch on the
controller. After the self test screen has been displayed, the pLAN address screen will be displayed.
Controller
Address 1
BluCube EEV
Driver
Address 9
Airedale REEV
Driver
Address 17
Remote Display
Address 32
The board address can also be changed be selecting Board Switch from the main menu:
The following screen will be displayed
The unit number can be changed to another number on the network.
Condensing Unit
BluCube™
Te
ch
nic
al