Health and Safety
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.
When working with any air conditioning units ensure that the electrical isolator is switched off prior
to servicing or repair work and that there is no power to any part of the equipment. Also ensure
that there are no other power feeds to the unit such as fi re alarm circuits, BMS circuits etc.
Electrical installation commissioning and maintenance work on this equipment should be
undertaken by competent and trained personnel in accordance with local relevant standards and
codes of practice.
A full hazard data sheet in accordance with COSHH regulations is available should this be required.
Personal Protective Equipment
Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning
equipment.
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual
handling. This requirement is down to the discretion of the engineer.
Remember do not perform a lift that exceeds your ability.
CAUTION
Refrigerant Warning
The Airedale unit uses R410A refrigerant which requires careful attention to proper storage and handling procedures.
Use only manifold gauge sets designed for use with R410A refrigerant. Use only refrigerant recovery units and cylinders
designed for high pressure refrigerants.
R410A must only be charged in the liquid state to ensure correct blend makeup.
The refrigerant must be stored in a clean, dry area away from sunlight. The refrigerant must never be stored above
50°C.
Maximum and Minimum Operation Temperature (Ts) and Pressure (Ps)
Operating Temperature (Ts),
Ts =
Min -20°C to Max 120°C *
Maximum Operating Pressure (Ps) Ps =
High Side 40.7 Barg
*Based upon the maximum machine running temperatures.
Glo
bal Warming Potential
The R410A refrigerant has a GWP of 1980 (based on EN378-1:2008+A2:2012, 100 year life)
Condensing Unit
BluCube™
3
BluCube Installation and Maintenance Manual 7222094 V1.12.0_04_2016