Installation and Maintenance Manual
22
Settings Page 1
1. Set points for unit. Depending on the unit this can be temperature, humidity or pressure
set points. They can be adjusted by using the up and down arrows;
2. Compressor pressure set points. It is recommended to keep these within the
recommended range to avoid premature wear or failure of the compressor;
3. Dead band for the thermostat. This is the temperature range for the set point. For
example, if the set point is 27 degrees and the dead band is 0.5 degrees the unit will
run so that the temperature in the room is between 26.5 and 27.5 degrees. It is
recommended to set dead bands to a minimum value of 0.5 to ensure stable operation.
4. Home button will take you back to the service page
5. Next button will take you to the next settings page