Installation and Maintenance Manual
10
Filters
IMPORTANT
Never operate the unit without filters fitted to the Return and Fresh Air intakes with
blower access panels removed.
Make-up air quantity (if any) is to be incorporated into outdoor air filtered airflow.
G4 panel and bag filters are included in standard units.
NOTE:
If these units are being used during construction when adhesive or sealants are in use, and
if ducts and carpets are being installed or removed, make sure all equipment is fitted and
adequately protected. We recommend using disposable or temporary filters during commissioning
and during pre
‐
hand over running.
Electrical/Electronic Connections
For power requirements and voltages, see the unit specifications.
The electrical diagram is attached on the wall of the electrical board cabinet.
Mains Power Supply and Fusing
A power supply rated at 415 V +/
‐
10% 3-phase or 240 V +/
‐
10% 1-phase, 50 Hz is required to
operate the machine within manufacturer's tolerances.
Mains cables are to be connected as per the wiring diagram.
Field wiring on the sensor and HLI communication to the controller (if any) need to be done on site.
The units require a mains circuit breaker or HRC fusing capable of handling the full load of the unit
and selected in accordance with SAA Wiring Rules to be fixed external to the unit.
A mains switch is fitted to the electrical board inside unit.
Electrical Connection and Supply Size Precaution
We recommend an isolator be mounted externally to the unit (not supplied) and a suitably sized
fuse mounted back at the distribution board to provide local isolation during service and
maintenance periods. The unit has a 3
‐
phase switch internally on the electrical board.