107110-01 - 6/16
XII. Operation
F. Changing Adjustable Parameters (continued)
Factory
Setting
Range /
Choices
Parameter and Description
Local
Local,
4-20mA
Central Heat Modulation Source
This parameter enables the 4-20mA input to control firing rate and the thermostat input to control boiler
on/off demand directly without using the internal setpoint. The 4-20mA selection is used to enable a
remote multiple boiler controller:
Local: 4-20mA Input on Control Terminals J8-6 and J10-8 is ignored.
4-20mA 4-20mA Input on Control Terminals J8-6 and J10-8 is used to control firing Rate %
directly.
Modbus Modbus input used to control firing Rate % directly.
Local
Local,
4-20mA
Central Heat Setpoint Source
Sets the remote (Energy Management System) control mode as follows:
Local: Local setpoint and modulation rate is used. 4-20mA input on Control Terminals J8-6 and
J10-8 is ignored.
4-20mA 4-20mA Input on Control Terminals J8-6 and J10-8 is used as the temperature setpoint.
The following two parameters may be used to adjust the signal range.
Modbus Modbus is used as the temperature setpoint.
130°F
(54.4°C)
80°F (26.7°C) -
Central Heat
Setpoint
Central Heat 4-20madc Setup, 4 ma Water Temperature*
Sets the Central Heat Temperature Setpoint corresponding to 4mA for signal input on Control
Terminals J8-6 and J10-8. Current below 4mA is considered invalid, (failed or incorrect wired input).
180°F
(82.2°C)
80°F (26.7°C) -
Central Heat
Setpoint
Central Heat 4-20madc Setup, 20 ma Water Temperature*
Sets the Central Heat Temperature Setpoint corresponding to 20mA for signal input on Control
Terminals J8-6 and J10-8. Current above 20mA is considered invalid, (failed or incorrect wired input).
Local
Local,
Modbus
Central Heat Demand Source
This parameter enables a Modbus input to be take the place of the Heating Thermostat Input:
Local
Local Heating Thermostat input is used for Central Heat demand.
Modbus Modbus input is used for Central Heat demand.
* Only visible when Central Heat Setpoint Source is set to 4-20mA.
“Press”
button to access the following parameters:
Содержание K2WT
Страница 11: ...11 107110 01 6 16 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 72: ...72 Figure 9 6 Piping Method 1 Near Boiler Piping Shaded Boiler Loop IX System Piping continued ...
Страница 82: ...82 107110 01 6 16 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Страница 83: ...83 107110 01 6 16 X Wiring continued Figure 10 5 Internal Ladder Diagram ...
Страница 84: ...84 107110 01 6 16 X Wiring continued ...
Страница 85: ...85 107110 01 6 16 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Страница 87: ...87 107110 01 6 16 Figure 10 8 TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram X Wiring continued ...
Страница 88: ...88 107110 01 6 16 X Wiring continued Figure 10 9 Sage Zone Control Circulator Panel Wiring Connection Diagram ...
Страница 95: ...95 107110 01 6 16 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Страница 140: ...140 107110 01 6 16 XV Repair Parts continued ...
Страница 142: ...142 107110 01 6 16 XV Repair Parts continued ...
Страница 146: ...146 107110 01 6 16 XV Repair Parts continued ...
Страница 148: ...148 107110 01 6 16 XV Repair Parts continued ...
Страница 161: ...161 107110 01 6 16 ...
Страница 162: ...162 107110 01 6 16 ...
Страница 163: ...163 107110 01 6 16 ...
Страница 164: ...164 107110 01 6 16 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...