81
107110-01 - 6/16
• Outdoor Sensor - Tasseron TSA00AA Outdoor Temperature Sensor (1)
• Outdoor Sensor - Tasseron TSA00AA Outdoor Temperature Sensor (2)
• Header Sensor - Optional Honeywell 32003971-003 (103104-01) Sensor (1)
• Header Sensor - Optional Honeywell 32003971-003 (103104-01) Sensor (2)
• MODBUS - (A)
• MODBUS - (B)
• MODBUS - (-V)
With the exception of the alarm contacts, external power must not be applied to any of the low voltage terminals - doing so
may damage the boiler control. Also note the following:
a) External Limit
- The external limit terminals are intended for use with a field supplied safety device, such as a manual
reset high limit. When an external limit is used, the jumper between these two terminals must be removed. Failure to
remove this jumper will render the external safety devices ineffective.
b) Alarm Contacts - These contacts close when the boiler enters a “hard” lockout (lockout requiring manual reset). They
may be used as an input to a building alarm system. Contact rating is 24VAC, 0.63FLA. Do not use for line voltage ap-
plications.
c) EnviraCOM - Used to connect EnviraCOM thermostat or other EnviraCOM device approved by the boiler manufacturer
for use with this boiler. A Honeywell EnviraCOM connection is also located as labeled on the boiler control itself.
d) Outdoor Sensor - Use only the Tasseron TSA00AA (10 KOhms) outdoor sensor supplied with the boiler. When this
sensor is connected and enabled, the boiler will adjust the target supply water temperature downwards as the outdoor
air temperature increases. This sensor should be located on the outside of the structure in an area where it will sense the
average air temperature around the house. Avoid placing this sensor in areas where it may be covered with ice or snow.
In general, locations where the sensor will pick up direct radiation from the sun should also be avoided. Avoid placing
the sensor near potential sources of electrical noise such as transformers, power lines, and fluorescent lighting. Wire the
sensor to the boiler using 22 gauge or larger wire. As with the sensor itself, the sensor wiring should be routed away from
sources of electrical noise. Where it is impossible to avoid such noise sources, wire the sensor using a 2 conductor, UL
Type CM, AWM Style 2092 shielded cable. Connect one end of the shielding on this cable to ground. See Section XII of
this manual for information on enabling the outdoor reset sensor.
e) Header Sensor - When this sensor is installed and enabled, the boiler will attempt to maintain the target water tempera-
ture in the header rather than in the supply. Where the system flow rate varies widely, the use of a header sensor al
-
lows the temperature of the water being sent to the radiation to be more accurately controlled. Use only the Honeywell
32003971-003 (103104-01) sensor listed above. Locate this sensor immediately downstream of the second primary-
secondary Tee (Figure 10.4). Installation of this sensor in a well, as opposed to on the surface of the header, is highly
recommended. The sensor wiring should be routed away from sources of electrical noise. Where it is impossible to avoid
such noise sources, wire the sensor using a 2 conductor, UL Type CM, AWM Style 2092, 300Volt 60°C shielded cable.
Connect one end of the shielding on this cable to ground. See Section XII for information on enabling the header sensor.
f) MODBUS - Boiler-To-Boiler communication network is used for multiple boiler (“Lead-Lag”) installations. See the
multiple boiler installation supplement for additional information.
X. Wiring
(continued)
CaUTiOn
When making low voltage connections, make sure that no external power source is present in the
thermostat or limit circuits. If such a power source is present, it could destroy the boiler’s control.
One example of an external power source that could be inadvertently connected to the low voltage
connections is a transformer in the old thermostat wiring.
Do not attempt to use EnviraCOM connections for any purpose not explicitly permitted by the boiler
manufacturer. Attempting to do so may result in unreliable operation and/or damage to controls.
Содержание K2WT
Страница 11: ...11 107110 01 6 16 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 72: ...72 Figure 9 6 Piping Method 1 Near Boiler Piping Shaded Boiler Loop IX System Piping continued ...
Страница 82: ...82 107110 01 6 16 Figure 10 4 Proper Installation of Header Sensor X Wiring continued ...
Страница 83: ...83 107110 01 6 16 X Wiring continued Figure 10 5 Internal Ladder Diagram ...
Страница 84: ...84 107110 01 6 16 X Wiring continued ...
Страница 85: ...85 107110 01 6 16 Figure 10 6 Internal Wiring Connections Diagram X Wiring continued ...
Страница 87: ...87 107110 01 6 16 Figure 10 8 TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram X Wiring continued ...
Страница 88: ...88 107110 01 6 16 X Wiring continued Figure 10 9 Sage Zone Control Circulator Panel Wiring Connection Diagram ...
Страница 95: ...95 107110 01 6 16 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Страница 140: ...140 107110 01 6 16 XV Repair Parts continued ...
Страница 142: ...142 107110 01 6 16 XV Repair Parts continued ...
Страница 146: ...146 107110 01 6 16 XV Repair Parts continued ...
Страница 148: ...148 107110 01 6 16 XV Repair Parts continued ...
Страница 161: ...161 107110 01 6 16 ...
Страница 162: ...162 107110 01 6 16 ...
Страница 163: ...163 107110 01 6 16 ...
Страница 164: ...164 107110 01 6 16 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...