DC Inverter U-match Series Cassette Type Unit
38
④.
The external power cord, connection wire of indoor and outdoor units and
the communication cords must be effectively fixed.
⑤.
The external power cord, connection wire of indoor and outdoor units and
the communication cords can’t directly contact any hot objects. For
example: they must not contact chimney pipes, warm gas pipes or other
hot objects.
⑥.
The external power cord, communication cords, and the connection wire
of indoor and outdoor units must not be squeezed. Never pull, stretch or
bend the wires.
⑦.
The external power cord, communication cords and the connection wire
of indoor and outdoor units must not collide with any metal beam or edge
on the ceiling, or touch any metal burrs or sharp metal edge around.
⑧.
Connect wires correspondingly by referring to the circuit diagram labeled
on the unit or electric box. Screws must be tightened up. Slipped screws
must be replaced by specialized flat-head screws.
⑨.
Please use the power cables that are delivered along with the air
conditioner. Do not change the power cables arbitrarily. Do not change
the length and terminals of the power cables. If you want to change the
power cables, please contact innova’s local service center.
⑩.
Wiring terminals should be connected firmly to the terminal board. Loose
connection is forbidden.
⑪
.
After the electrical installation is finished, please use wire clamps to
secure the power cord, connection wire of indoor and outdoor units and
the communication cords. Make sure the wires are not clamped too tight.
⑫
.
The wire gauge of power cord should be large enough. Damaged power
cord or other wires must be replaced by specialized wires. Wiring work
must be done according to national wiring rules and regulations.
3.3.2 Electrical Parameters
Model
Power supply
Fuse
capacity
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
A
mm
2
Indoor
unit
220V-240V ~50Hz
208V-230V ~60Hz
3.15
6
1.0
Содержание Innova IGZCAPB100NI-1
Страница 9: ...DC Inverter U match Series Cassette Type Unit 5 2 Product Introduction 2 1 Overall Layout ...