E1463A Command Reference 55
Chapter 3
INITiate
The INITiate command subsystem selects continuous scanning cycles and
starts the scanning cycle.
Subsystem Syntax
INITiate
:CONTinuous <mode>
:CONTinuous?
[:IMMediate]
INITiate:CONTinuous
INITiate:CONTinuous <mode>
enables or disables continuous scanning
cycles for the switchbox.
Parameters
Comments
Continuous Scanning Operation:
Continuous scanning is enabled with
INITiate:CONTinuous ON or INITiate:CONTinuous 1. Sending
INITiate:IMMediate closes the first channel in the channel list. Each trigger
from the source specified by TRIGger:SOURce advances the scan through
the channel list. A trigger at the end of the channel list closes the first
channel in the channel list and the scan cycle repeats.
Noncontinuous Scanning Operation
: Noncontinuous scanning is enabled
with INITiate:CONTinuous OFF or INITiate:CONTinuous 0. Sending
INITiate:IMMediate closes the first channel in the channel list. Each trigger
from the source specified by TRIGger:SOURce advances the scan through
the channel list. At the end of the scanning cycle, the last channel in the
channel list is opened.
Stopping Continuous Scan:
See the ABORt command.
Related Commands:
ABORt, ARM:COUNt, TRIGger:SOURce
*RST Condition:
INITiate:CONTinuous OFF | 0
Name
Type
Range of Values
Default Value
<mode>
boolean
ON | OFF | 1 | 0
OFF | 0