Page 88
22.10.2019
R01.43
Firmware update process current client node (1)
If a firmware update process is already active, the client node serial number used
there is displayed.
INSTRUCTION
It is not possible to provide a firmware update for several client
nodes simultaneously. For this reason, the currently used Client
Node Serial is displayed.
Procedure for installing a new client firmware:
1. Select .hex firmware file (2)
The desired .hex firmware file must be selected. The correct client node type must
be observed.
2. Start transfer (3)
If the firmware file is loaded, the display bar jumps to 100% and the button to start
the transfer is released. By clicking on this, the flash memory of the client node is
deleted and then the new firmware file is transferred.
3. Start firmware (4)
As soon as the firmware file has been transferred fully, the button for starting the
firmware is released. Clicking on this activates the firmware of the client node. It is
displayed as "connected" and the normal client node functions are available.
INSTRUCTION
If no valid firmware is present on the client node, this automati-
cally returns to the bootloader mode.
4. Cancel update firmware (5)
If the firmware update is to be cancelled, this button is to be pressed. The current
process is terminated. If data has already been transferred, the flash memory of
the client node is deleted. A valid firmware must be transferred completely in order
to run it outside the bootloader mode.
Содержание aflex 150 qc
Страница 36: ...Page 36 22 10 2019 R01 43 ...
Страница 100: ...Page 100 22 10 2019 R01 43 Figure 79 Fieldbus Konfiguration IO Typ 3 ...