COLD W
ATER TEMPERA
TURE °C
HOT WATER TEMPERATURE °C
25
30
35
40
45
50
55
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
-6
13.87
2.88
13.59
3.27
13.31
3.69
13.03
4.30
12.75
4.72
-
-
-
-
-4
14.90
2.86
14.58
3.25
14.27
3.67
13.96
4.25
13.67
4.68
-
-
-
-
-2
15.93
2.84
15.58
3.23
15.23
3.66
14.90
4.21
14.58
4.64
14.32
5.33
-
-
0
16.96
2.82
16.57
3.21
16.19
3.64
15.83
4.16
15.50
4.60
15.22
5.28
-
-
2
18.00
2.81
17.57
3.19
17.16
3.62
16.76
4.12
16.42
4.56
16.12
5.23
-
-
4
19.03
2.79
18.56
3.17
18.12
3.61
17.70
4.07
17.33
4.52
17.02
5.17
16.55
5.65
6
19.55
2.78
19.06
3.16
18.60
3.60
18.16
4.05
17.79
4.50
17.47
5.15
16.93
5.65
7
20.19
2.77
19.67
3.15
19.18
3.58
18.71
4.04
18.30
4.50
17.94
5.14
17.39
5.67
8
21.47
2.75
20.89
3.13
20.34
3.55
19.80
4.01
19.31
4.50
18.88
5.14
18.32
5.69
10
22.74
2.72
22.11
3.11
21.50
3.51
20.89
3.99
20.33
4.50
19.83
5.13
19.25
5.72
12
24.02
2.70
23.33
3.10
22.66
3.48
21.98
3.96
21.34
4.50
20.77
5.12
20.19
5.75
14
25.30
2.68
24.55
3.08
23.82
3.44
23.08
3.94
22.36
4.50
21.71
5.11
21.12
5.78
16
26.58
2.66
25.77
3.06
24.98
3.41
24.17
3.91
23.37
4.51
22.66
5.11
22.05
5.81
18
27.86
2.64
26.99
3.04
26.14
3.38
25.26
3.89
24.39
4.51
23.60
5.10
22.98
5.83
HEATING CAPACITY / INPUT POWER (KW)
11.16.
VXT 16 400V
DATA DECLARED ACCORDING TO EN 14511:2004
FOR
∆
T DIFFERENT FROM
11.17.
NOMINAL
For
∆
t different to 5°C, use the table
to obtain the corrective factors of the
cooling/heating capacity and input
power.
DEPOSIT FACTORS
11.18.
The performance supplied by the table
refer to clean pipe conditions with
deposit factor = 1. For different deposit
factor values, multiply the performance
table data by the coefficients given.
3
5
8
10
Cooling capacity correction factors
0,99
1
1,02
1,03
Heating capacity correction factors
0,99
1
1,02
1,03
Input power correction factors
0,99
1
1,01
1,02
5
10
15
Cooling capacity correction factors
1
1,01
1,02
Input power correction factors
1
0,99
0,98
The variations can be ignored for the heating capacity
For
∆
t different on the evaporator
For
∆
t different on the condenser
[K*m
2
]/[W]
0,00001
0,00002
0,00005
Cooling capacity correction factors
1
0,99
0,98
Input power correction factors
1
1
1
Heating capacity correction factors
1
1
0,99
Input power correction factors
1
1
1,02
Deposit factors
11.18.1.