The functioning limits diagram is
relative to a
∆
t on the evaporator and
on the condenser of 5°C.
OPERATIONAL LIMITS
10.
YIELDS AND ABSORPTION AT CONDITIONS
11.
DIFFERENT TO NOMINAL
Condenser water outlet temperature °C
Evaporator water outlet temperature °C
60
55
50
45
40
35
30
25
20
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
20
Glycoled
Water
Standard
Functioning
CONDENSER W
ATER TEMPERA
TURE °C
EVAPORATOR WATER TEMPERATURE °C
25
30
35
40
45
50
55
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
Pt
Pa
-6
5.67
1.28
5.55
1.45
5.44
1.64
5.32
1.91
5.21
2.10
-
-
-
-
-4
6.05
1.27
5.94
1.44
5.83
1.63
5.73
1.91
5.63
2.12
-
-
-
-
-2
6.42
1.26
6.32
1.43
6.22
1.63
6.14
1.90
6.05
2.14
5.85
2.37
-
-
0
6.80
1.26
6.71
1.43
6.62
1.62
6.54
1.90
6.47
2.16
6.31
2.37
-
-
2
7.18
1.25
7.10
1.42
7.01
1.61
6.95
1.89
6.89
2.18
6.76
2.37
-
-
4
7.56
1.24
7.48
1.41
7.40
1.60
7.36
1.89
7.31
2.20
7.22
2.37
7.30
2.56
5
7.75
1.24
7.68
1.41
7.60
1.60
7.56
1.89
7.52
2.21
7.45
2.38
7.37
2.54
6
8.04
1.23
7.94
1.40
7.84
1.59
7.77
1.87
7.71
2.19
7.61
2.37
7.52
2.55
8
8.61
1.22
8.46
1.39
8.31
1.58
8.19
1.84
8.07
2.15
7.93
2.34
7.81
2.55
10
9.18
1.21
8.98
1.38
8.78
1.56
8.61
1.82
8.43
2.11
8.26
2.32
8.10
2.56
12
9.75
1.20
9.50
1.38
9.26
1.55
9.02
1.79
8.80
2.06
8.58
2.30
8.38
2.57
14
10.32
1.19
10.02
1.37
9.73
1.53
9.44
1.76
9.16
2.02
8.90
2.28
8.67
2.57
16
10.89
1.18
10.54
1.36
10.21
1.52
9.86
1.73
9.52
1.98
9.23
2.26
8.96
2.58
18
11.46
1.17
11.06
1.35
10.68
1.50
10.28
1.70
9.89
1.94
9.55
2.24
9.25
2.58
HEATING CAPACITY / INPUT POWER (KW)
11.1.
VXT 06 230V
High pressure
side
Low pressure
side
Acceptable maximum pressure
bar
42
25
Acceptable maximum temperature
°C
120
52
Acceptable minimum temperature
°C
-10
-16
PROJECT DATA
DATA DECLARED ACCORDING TO EN 14511:2004
16