VXT 06
VXT 08
VXT 10
VXT 14
VXT 16
HEATING
Heating capacity
400V
kW
7.52
9.47
11.76
16.24
17.79
Total input power
400V
kW
2.07
2.46
3.00
4.00
4.50
Condenser water capacity (user)
400V
l/h
1,290
1,630
2,020
2,790
3,060
Available useful static pressures (user)
400V
kPa
33
45
47
46
45
Water consumption at the evaporator
400V
l/h
960
1230
1530
2140
2320
Evaporator pressure drop
400V
kPa
6
11
8
8
8
Geothermic pump useful static pressure if envisioned
400V
kPa
43
56
47
56
56
COOLING
Cooling capacity
400V
kW
6.39
8.21
10.30
13.38
15.26
Total input power
400V
kW
1.61
1.92
2.41
3.32
3.52
Evaporator water capacity (user)
400V
l/h
1100
1410
1770
2300
2620
Available useful static pressures (user)
400V
kPa
54.2
47.6
47.9
40.5
38.5
Water consumption at the condenser
400V
l/h
1360
1730
2170
2840
3200
Condenser pressure drop
400V
kPa
13
21
15
15
15
Geothermic pump useful static pressure if envisioned
400V
kPa
32
43
46
44
43
ENERGETIC INDEX
COP* (UNI EN 14511:2004)
W/W
3.63
3.85
3.92
4.06
3.95
EER* (UNI EN 14511:2004)
W/W
3.97
4.28
4.27
4.03
4.34
ELECTRICAL DATA
Total input power (when HOT)
400V
A
4.2
4.6
6.3
8.9
8.8
Total input power (when COLD)
400V
A
3.6
3.4
5.3
7.3
7.5
Maximum current (FLA)
400V
A
5.5
6.0
8.0
10.0
11.8
Peak current with soft-start (LRA)
400V
A
32.0
35.0
48.0
64.0
64.0
SCROLL (COMPRESSORS)
Number per circuit
n°
1/1
1/1
1/1
1/1
1/1
REFRIGERANT GAS
R410A
DOMESTIC HOT WATER DHW MAXIMUM TEMPERATURE
Continuous distribution of domestic hot water at the flow rate of
12 lt/min. and temperature of 40°C
min.
12
13.5
15
16
16.5
EVAPORATOR (PLATES)
Number
n°
1
1
1
1
1
CONDENSER (PLATES)
Number
n°
1
1
1
1
1
WATER/WATER HEAT EXCHANGER (PLATES)
Number
n°
1
1
1
1
1
STORAGE TANK
Amount of water
lt.
180
180
180
180
180
PUMP SIDE UTILITIES/GEOTHERMIC
Input power
W
85
110
110
175
175
DHW SIDE PUMP
Input power
W
50
50
50
50
50
INTEGRATIVE RESISTANCES IF ENVISIONED
Resistance power
W
1X2000 1X3000 2X2000 2X3000 2X3000
HYDRAULIC CONNECTIONS
System water inlet/outlet
IN/OUT
Ø
1” F
1” F
1” F
1” F
1” F
Domestic hot water inlet/outlet
IN/OUT
Ø
3/4” M
3/4” M
3/4” M
3/4” M
3/4” M
Sheet inlet/outlet
IN/OUT
Ø
1” F
1” F
1” F
1” F
1” F
SOUND DATA
Sound power
dB(A)
43
45
45
47
49.5
Sound Pressure
dB(A)
35
37
37
39
41.5
400V 3N
8.4.
~ 50Hz fan coils
NOMINAL REFERENCE
8.4.1.
CONDITIONS
HEATING:
- Condenser IN/OUT water temp.
40/45 °C
- Evaporator IN/OUT water temp.
10/5 °C
-
∆
t
5
°C
COOLING:
- Evaporator IN/OUT water temp.
12/7 °C
- Condenser IN/OUT water temp.
30/35 °C
-
∆
t
5 °C
SOUND DATA
Sound power
Aermec determines sound power values with
measurements taken in agreement with the 9614-2
Standard, in compliance with that requested by Eurovent
certification.
Sound Pressure
Environment volume of 80m3, reverberation time 0.5s,
distance 3 metres and directionality factor 4.
FLA
= Max. Input current at full load
LRA
= Peak current at full load
DATA DECLARED ACCORDING TO EN 14511:2004
14