47
EN
ModBus Address
Content
Range
Default
Posizione Record
00
Useless
Main Control
01
Useless
Main Control
02
By-pass opening temperature X
5-30
19 °C
Main Control
03
By-pass opening temperature range Y
2-15
3 °C
Main Control
04
Defrosting interval
15-99
30 min
Main Control
05
Defrosting enter temperature
-9….+5
-1 °C
Main Control
06
Defrost duration time
2-20
10 min
Main Control
07
CO
2
sensor
28-C8 (392-1960ppm)
66 (1000ppm)
Main Control
08
ModBus address
1-16
Main Control
09
ERV ON/OFF
0-OFF 1-ON
Main Control
10
Supply fan speed
Fan speed:
0= stop, 2= speed 1
3= speed 2, 5= speed 3,
8= speed 4, 9= speed 5,
10= speed 6, 11= speed 7,
12= speed 8, 13= speed 9,
14= speed 10.
Main Control
11
Exhaust fan speed
Fan speed:
0= stop, 2= speed 1
3= speed 2, 5= speed 3,
8= speed 4, 9= speed 5,
10= speed 6, 11= speed 7,
12= speed 8, 13= speed 9,
14= speed 10.
Main Control
12
Room temperature
observed value
Main Control
13
Outdoor temperature
observed value
Main Control
14
Exhaust air temperature
observed value
Main Control
15
Defrosting temperature
observed value
Main Control
16
External ON/OFF signal
observed value
Main Control
17
CO
2
ON/OFF signal
observed value
Main Control
18
Fire alarm signal/bypass/defrosting
signal
query value:
B0 - 1- fire alarm ON
B1 - 1- by-pass ON
B2 - 1- by-pass OFF
B3 - 1- defrosting
Main Control
19
Electrical heater stage
Main Control
20
Error symbol
query value:
B2 - OA - temperature error
B5 - EEPROM error
B4 - RA - temperature error
B3 - Fr - temperature error
(auto defrosting)
Main Control
21
ERV models selection
22
Defrosting models
TABLE OF MODBUS ADDRESS
Содержание Novatherm TRS Series
Страница 27: ...27 IT SCHEMA DEI COMPONENTI ...
Страница 39: ...39 EN WIRING DIAGRAMS TRS USW TRS PTS TRS QSW ...
Страница 52: ...52 EN COMPONENTS DIAGRAM ...
Страница 77: ...77 FR SCHÉMA DES COMPOSANTS ...
Страница 102: ...102 DE SCHEMA DER KOMPONENTEN ...
Страница 127: ...127 ES ESQUEMA DE LOS COMPONENTES ...
Страница 129: ...129 ES ...
Страница 130: ...130 ES ...
Страница 131: ...131 ES ...