42
EN
Speed 3
Error Alarm
Speed 5
Speed 10
Error Alarm
Current Humidity
Setting Humidity
SA Temperature Setting
CO
2
Concentration
Remark:
The CO
2
symbol appears when the CO
2
sensor is connected. ERV runs at boost speed when CO
2
concentration higher than setting value.
The humidity symbol appears when the “temperature and humidity sensor” is connected. ERV runs at boost speed when humidity higher
than setting value. Under “humidity control” mode, users can set the setting humidity by pressing
▲
and
▼
keys. The setting range
is 45% ~ 90%. And the Dial switch SW4-3 on the PCB should be switched ON to switch from CO
2
control function to humidity control
function.
2.
Mode key:
press the MODE key to select the RA-OA-FR (ea)-sa setting-CO
2
status or humidity control.
3.
Adjusting the air flow:
access the SA (supply) or RA (return) temperature visualisation. The user can set the return air flow
in RA mode, and the supply air flow in SA mode, by pressing the
▲
and
▼
keys. There is a choice of 10 speed levels.
4.
Checking the error code:
from the main screen, press the SET key briefly to check the fan error code. Refer to the table
below.
5.
Setting the bypass:
when the bypass is active, the Δ bypass signal appears (disappearing when the bypass is deacti-
vated). Refer to the chapter with the detailed explanation of the settings.
CODICE
ERRORE
E1
Fresh air temperature sensor error
E2
EEPROM error
E3
Error on return air temperature sensor
E4
Error on expelled air temperature sensor
E5
Communication error
E6
Supply air temperature sensor error
E7
Expulsion fan error
E8
Supply fan error
Содержание Novatherm TRS Series
Страница 27: ...27 IT SCHEMA DEI COMPONENTI ...
Страница 39: ...39 EN WIRING DIAGRAMS TRS USW TRS PTS TRS QSW ...
Страница 52: ...52 EN COMPONENTS DIAGRAM ...
Страница 77: ...77 FR SCHÉMA DES COMPOSANTS ...
Страница 102: ...102 DE SCHEMA DER KOMPONENTEN ...
Страница 127: ...127 ES ESQUEMA DE LOS COMPONENTES ...
Страница 129: ...129 ES ...
Страница 130: ...130 ES ...
Страница 131: ...131 ES ...