44
EN
(*) For spare parts only. The value is correctly set for each machine during the testing phase.
Instruction of parameter Settings
1) Parameter 00 refers to power to auto restart 0: Invalid, 1: Valid.
2) Parameter 01 refers to Supply air electrical heater function 0: not available 1: available (function not available).
When connecting with supply air electrical heater, user should choose 1 to activate the electrical heater, and under the SA temperature
setting interface, the SA temperature can be set by pressing up and down button. The setting temperature range is 10 - 25° C.
3) Parameter 02 - 03 refers to automatic bypass function The bypass is opened on the condition that the outdoor temperature is
equal or higher than X (parameter 02) and less than X+Y (parameter 03). Bypass is closed on other conditions
4) Parameter 04-06 refers to automatic defrost function when EA side of heat exchanger temperature lower than -1°C (defrosting
entering temperature, parameter 05) and last for 1 minute, and the interval of defrosting is longer than 30 minutes (parameter 04),
the exhaust fan will run at high speed automatically for defrosting, and supply fan will stop, until EA side temperature higher than
defrosting entering tempe15°C for 1 minute, or the defrosting time is longer than 10 minutes (parameter 06).
5)Parameter 07 refers to CO
2
concentration control function (optional) After connecting the CO
2
sensor (TRSQSW accessory), the
CO
2
symbol will display on the screen. If CO
2
concentration is higher than setting value, then ERV returns back to the previous status
(standby, speed 1, 2, 3 etc.), if the ERV is already in highest speed when CO
2
concentration higher than setting value, then ERV keeps
the highest speed running. CO
2
default setting value is 00, which means CO
2
function off. setting range is 80- 250, which means 800-
2500PPM (concentration/10 in steps of 10), recommended value 1000PPM.
6) Parameter 08 refers to the central control function to identify the address of ERV.
7) Parameter 21 to match the suitable program on PCB to the ERV model, refer to below table.
8) Parameter 23 refers to the fan speed display, for the ERV with BLDC motor, user should change value to 2 for 10 speed control
9) Parameter 24 refers to clear filter alarm and weekly timer setting:
•
setting this parameter = 1, the filter alarm is reset by timer, according to the setting chosen at the next parameter 25 (when the time
set in parameter 25 expires, the filter timer alarm appears, which can be reset by setting the parameter 24);
•
setting this parameter = 2 resets the weekly timer.
Once assigned the value 1 or 2, this parameter is repositioned to 0.
10) Parameter 25 refers to set the filter alarm timer.
No. Contents
Range
Default Unit
Record Position
00
Power to auto restart
0-1
1
Main control
01
Electrical heater (n.d.)
0-1
0
Main control
02
y pass opening temperature X
5-30
19
°C
Main control
03
By pass opening temperature Y
2-15
3
°C
Main control
04
Defrost interval
15-99
30
Minute
Main control
05
Defrost entering temperature
-9….+5
-1
°C
Main control
06
Defrost duration time
2-20
10
Minute
Main control
07
CO
2
sensor function value
80-250
00
PPM
Main control
08
ModBus address
1-16
1
Main control
21
ERV models match selection
0-9
0 (*)
Main control
23
Fan speed control
0 = 2 speeds
1 = 3 speeds
2 = 10 speeds
2
24
Multifunction setting
0 = n.d.
1 = Sweep filter alarm
2 = Sweep weekly timer
0
25
Filter alarm setting
0 = 45 days
1 = 60 days
2 = 90 days
3 = 180 days
0
Main control
MODELLO
CODICE ERV
TRS251
5
TRS351
4
TRS501
3
TRS651
7
TRS801
8
TRS1001
9
TRS1301
8
Содержание Novatherm TRS Series
Страница 27: ...27 IT SCHEMA DEI COMPONENTI ...
Страница 39: ...39 EN WIRING DIAGRAMS TRS USW TRS PTS TRS QSW ...
Страница 52: ...52 EN COMPONENTS DIAGRAM ...
Страница 77: ...77 FR SCHÉMA DES COMPOSANTS ...
Страница 102: ...102 DE SCHEMA DER KOMPONENTEN ...
Страница 127: ...127 ES ESQUEMA DE LOS COMPONENTES ...
Страница 129: ...129 ES ...
Страница 130: ...130 ES ...
Страница 131: ...131 ES ...