49
IFCLITY1106 - 5773010_01
ELECTRICAL WIRINGS
The unit must be connected directly to an
electrical outlet or to an independent
circuit.
The FCLI cassette-type fan coils must
be powered with a current of 230V
~50Hz with an earth connection;
the line voltage must however
remain within the tolerance of ±10%
compared with the nominal value.
To protect the unit against short circuits,
fit an omnipolar thermal trip max.
2A 250V (IG) to the power line with
a minimum contact opening distance
of 3 mm.
The electrical power cable must be of
the H07 V-K or N07 V-K type with
450/750V insulation if inside a tube
or raceway. Use cables with double
H5vv-F type insulation for visible cable
installation.
For all the connections, follow the wiring
diagrams supplied with the device and
shown in this documentation.
The electric box is supplied with
obligatory accessories (GLLI - GLLI_N).
Connect the Inverter to the electric box, using the
cables supplied.
WARNING: Do not modify the settings of the
Inverter device. Any modification to the
parameters could cause the device to
malfunction. The factory settings are shown on
the label attached to the unit.
Inverter device installed on a "module 600" unit
Inverter device installed on a "module 840" unit
The 4 connectors between the unit and
inverter are different.
This makes the fitters' work easier and prevents
erroneous connections.