IFCLITY1106 - 5773010_01
COOLING CAPACITY - FCLI 32 / FCLI34
Tw [°C]
= Inlet water temperature
Ta W.B. [°C]
= Inlet air temperature with wet bulb
Ta D.B.[°C]
= Inlet air temperature with dry bulb
Pc [W]
= Total cooling capacity
Ps [w]
= Sensible cooling capacity
NB: The values in bold type indicate the nominal value.
If sensible power values are above the total cooling capacity, this
means that cooling is carried out without dehumidification.
In this case, only sensible power values are considered.
The cooling outputs of the table are at maximum speed (maximum
air flow).
To determine the cooling capacity based on the speed (air flow),
the values shown in the table must be multiplied by the following
factors (k):
FCLI 32 / FCLI34
Qv
[m
3
/h]
k (Pc)
k (Ps)
Speed V3
600
1
1
Speed V2
410
0.77
0.82
Speed V1
300
0.61
0.65
Tw
[°C]
T [°C]
Ta W.B.
[°C]
Pc [W]
Ps [W]
Pc [W]
Ps [W]
Pc [W]
Ps [W]
Pc [W]
Ps [W]
Pc [W]
Ps [W]
Pc [W]
Ps [W]
21°C Ta D.B.
23°C Ta D.B.
25°C Ta D.B.
27°C Ta D.B.
29°C Ta D.B.
30°C Ta D.B.
5
3
15
1526
1281
1519
1457
1526
1526
1574
1574
1722
1722
1797
1797
17
1969
1274
1965
1454
1961
1631
1957
1808
1951
1951
1953
1953
19
2448
1264
2442
1444
2436
1623
2430
1800
2424
1975
2420
2062
21
2955
1430
2947
1609
2939
1786
2931
1963
2929
2052
23
3497
1591
3493
1773
3481
1948
3477
2037
5
15
1317
1164
1347
1347
1404
1404
1502
1502
1653
1653
1728
1728
17
1785
1174
1781
1353
1775
1530
1783
1711
1803
1803
1823
1823
19
2270
1169
2266
1349
2262
1528
2258
1707
2254
1882
2246
1968
21
2784
1340
2777
1519
2773
1698
2767
1875
2765
1963
23
3335
1506
3327
1684
3319
1862
3315
1951
7
15
1056
1014
1154
1154
1261
1261
1407
1407
1564
1564
1643
1643
17
1518
1035
1515
1213
1540
1400
1589
1589
1654
1654
1698
1698
19
2056
1059
2052
1239
2048
1417
2040
1592
2044
1771
2048
1861
21
2587
1239
2579
1417
2575
1595
2571
1773
2567
1860
23
3145
1410
3141
1590
3133
1767
3129
1855
7
3
15
1185
1093
1201
1201
1266
1266
1417
1417
1567
1567
1641
1641
17
1631
1093
1627
1271
1621
1448
1620
1620
1649
1649
1670
1670
19
2108
1085
2104
1265
2100
1444
2092
1618
2090
1794
2084
1880
21
2614
1254
2606
1432
2092
1618
2595
1785
2593
1873
23
3156
1417
3153
1597
3145
1774
3141
1862
5
15
978
974
1064
1064
1188
1188
1344
1344
1498
1498
1573
1573
17
1417
984
1412
1161
1431
1345
1472
1472
1534
1534
1586
1586
19
1912
987
1908
1166
1906
1345
1900
1520
1898
1696
1902
1787
21
2428
1161
2424
1341
2420
1518
2412
1693
2411
1781
23
2978
1329
2974
1508
2967
1685
2963
1773
7
15
762
762
917
917
1083
1083
1247
1247
1407
1407
1485
1485
17
1069
812
1132
1014
1213
1213
1307
1307
1417
1417
1488
1488
19
1643
857
1643
1037
1638
1213
1654
1397
1692
1587
1714
1682
21
2203
1053
2199
1231
2195
1408
2191
1584
2191
1672
23
2769
1229
2765
1408
2757
1583
2757
1673
9
3
15
862
862
956
956
1109
1109
1261
1261
1411
1411
1485
1485
17
1268
910
1262
1085
1275
1266
1314
1314
1415
1415
1488
1488
19
1748
907
1744
1086
1740
1263
1734
1437
1730
1612
1733
1701
21
2252
1077
2246
1254
2242
1431
2238
1608
2234
1693
23
2796
1243
2790
1421
2784
1597
2781
1685
5
15
709
709
865
865
1027
1027
1186
1186
1341
1341
1417
1417
17
996
778
1039
970
1110
1110
1207
1207
1344
1344
1420
1420
19
1521
800
1518
978
1515
1155
1524
1335
1553
1519
1575
1575
21
2044
980
2040
1157
2037
1333
2033
1509
2031
1595
23
2598
1151
2595
1329
2587
1504
2587
1593
7
15
536
536
739
739
917
917
1086
1086
1249
1249
1328
1328
17
645
599
800
800
944
944
1088
1088
1251
1251
1330
1330
19
1159
637
1167
817
1213
1010
1284
1211
1368
1368
1415
1415
21
1775
859
1771
1035
1771
1212
1775
1390
1787
1482
23
2361
1045
2357
1222
2353
1398
2349
1485
COOLING CAPACITY CORRECTION FACTORS