11
IFCLITY1106 - 5773010_01
TECHNICAL DATA
FCLI 2-pipe versions
FCLI
32
42
62
82
122
Heating
Heating output 50°C
Speed 4 W
-
4950
6250
7100
13000
Speed 3 W
2380
3940
4780
5700
10500
Speed 2 W
1760
3030
3830
4850
8800
Speed 1 W
1330
2250
3050
3500
6300
Pressure drop (VL)
Speed 4 kPa
-
23
32
23
34
Speed 3 kPa
9
16
21
15
24
Speed 2 kPa
6
10
15
11
17
Speed 1 kPa
4
6
10
6
9
Cooling
Cooling capacity
Speed 4 W
-
3950
4980
6000
11000
Speed 3 W
1900
3250
3940
4790
8950
Speed 2 W
1470
2540
3210
4050
7500
Speed 1 W
1160
1960
2660
2800
5360
Sensible cooling capacity
Speed 4 W
-
3160
3810
4200
8470
Speed 3 W
1520
2360
2810
3300
6870
Speed 2 W
1250
1820
2270
2770
5730
Speed 1 W
990
1380
1860
1900
4040
Water fl ow rate
Speed 4 l/h
-
679
857
1032
1892
Speed 3 l/h
327
559
678
824
1539
Speed 2 l/h
253
437
552
697
1290
Speed 1 l/h
200
337
458
482
922
Pressure drop (VL)
Speed 4 kPa
-
25
36
25
38
Speed 3 kPa
10
18
24
17
26
Speed 2 kPa
7
11
16
12
19
Speed 1 kPa
4
7
12
6
10
Common data
Fans
no.
1
1
1
1
1
Air fl ow rate
Speed 4 m3/h
-
700
880
1100
1750
Speed 3 m3/h
600
530
660
830
1350
Speed 2 m3/h
410
360
500
680
1100
Speed 1 m3/h
300
260
380
460
750
Sound power
Speed 4 dB(A)
-
53
61
50
60
Speed 3 dB(A)
46
46
54
45
54
Speed 2 dB(A)
38
38
47
43
50
Speed 1 dB(A)
35
35
41
39
44
Sound pressure
Speed 4 dB(A
-
44
52
41
51
Speed 3 dB(A
37
37
45
36
45
Speed 2 dB(A
29
29
38
34
41
Speed 1 dB(A)
26
26
32
30
35
Input power
Speed 4 W
-
75
83
150
175
Speed 3 W
45
47
53
105
125
Speed 2 W
31
32
37
80
105
Speed 1 W
21
22
26
45
55
Input current (max speed)
A
0.22
0.33
0.37
0,70
0.75
Starting current
A
0.66
0.99
1.11
2.10
2.25
Power supply
V / Hz
230V~50Hz
Maximum protection level
IP
20
20
20
20
20
Heat exchanger water content
L
1.2
1.5
2.1
3
4.5
Water connections
Ø gas
3/4”
3/4”
3/4”
3/4”
3/4”
Kvs (3-way valve, standard version)
2.5
2.5
2.5
4
4
Kvs (2-way valve, V2 version)
2.5
2.5
2.5
2.5
2.5
Level of sound pressure (A-weighted) measured in the room with
volume V = 100 m
3
, reverberation time t = 0.5 s; direction factor
Q = 2; distance r = 2.5m
Cooling:
• External air temperature 27°C D.B. ; 19°C W.B.
•
Water inlet temperature 7°C ;
t water 5°K
Heating 50°C:
• External air temperature 20°C
•
Water inlet temperature: 50°C;
t water 10°K
Heating 70°C:
• External air temperature 20°C
•
Water inlet temperature: 50°C;
t water 10°K
The leakage current to earth of several
devices placed under the same circuit
breaker is summed, so attention should be
paid to the calibration of the circuit breaker
and possibly consider the division of the
installation into several circuits each of
which protected by its own circuit breaker.
= Performance certified EUROVENT 6/3 - Sound tests certified EUROVENT 8/2 (ISO 3741/2001)
Performance values refer to the following conditions: