TF7039GB_A_NOT
Page 19 of 48
TECHNICAL DATA
Eco+ 111:
DIMENSIONING INFORMATION
Installation site
Outside
Pressure increase for dimensioning
Pa
130
Max. flow rate for dimensioning (75%) at 130 Pa
m³/h
2.400
Heating capacity modulation range (A20W35)
kW
2,5-8,4
Corresponding modulation range exhaust air
m³/h
480-1.800
Min. required effective exhaust air volume flow
m³/h
480
Max. flow temperature
°C
55
Sound pressure level at a distance of 3 metres from the design
(75%) - L
p, A
dB(A)
54
Sound power level on the suction side for dimensioning (75%) - L
w, A
dB(A)
66
CONNECTION TO THE PIPE NETWORK
Exhaust air
– pipe connection (DN)
mm
355
Exhaust air
– connection options
1 x horizontal
Elastic connector for pipe connection
integrated
Heat sink medium
– pipe connection
1” IG
Heat sink medium
– max. volume flow
m³/h
1,382
Heat sink medium
– permissible antifreeze agent
Ethylene glycol
Heat sink medium
– available external delivery pressure
kPa
48
Condensate
– pipe connection
Metal composite pipe (16 mm)
ENERGY DATA
Max. recoverable exhaust air heat
– heating period
MWh
27
Nominal heat output / COP (A20W35)
5,6 / 6,0
Nominal heat output / COP (A20W35)
5,6 / 8,2
COP (A20W40)
4,9
Refrigerant
R410A
Refrigerant fill level
1,9
VENTILATION AND ACOUSTIC DATA FOR FURTHER OPERATING POINTS
Max. volume flow (100%) at 130 Pa
m³/h
2.200
Sound pressure level at a distance of 3 metres at 100/50% - L
p, A
dB(A)
61/46
Sound power level on the suction side at 100/50% - L
w, A
dB(A)
67/59
INTEGRATED PRESSURE CONTROL
Digital pressure control display
integrated
Max. pressure increase
Pa
300
ELECTRICAL DATA
Fan
– drive technology
EC motor
Compressor
– drive technology
source-oriented performance-controlled
Repair switch
integrated
Supply voltage
V / Hz
230 / 50
Max. power consumption
A
12,3
Fan power consumption for dimensioning (75%) at 130 Pa
W
224
SFP fan for dimensioning (75%) at 130 Pa
W/m³/h
0,136
Max. fan power consumption
W
450
Max. fan power consumption (unit total)
kW
2,42
Motor protection type (fan)
IP
54
Motor protection (fan)
integrated
Contact for external release of heat pump components
integrated
Fault message
Contact for group alarm, digital display on the unit
Max. permissible exhaust air temperature
°C
40
HOUSING PROPERTIES
Weight (empty complete unit)
kg
325
Material
Steel (galvanised)
OTHER COMPONENTS
Filter class (with filter monitoring)
G4
Condensate tray with siphon
integrated
Smoke detector and bypass for free outflow
integrated
Heat sink medium feed pump (speed controlled)
integrated
All data for exhaust air at 20°C and 50% rel. humidity and for water. Data according to EN 14511:2013