MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
Page
30
of
146
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0087_0F
07/13/15
Phone: 800-526-0288
GF-143
Figure 3-6: Boiler (Front View) on Housekeeping Pad with Condensate Drain Pipe
Boiler Room Safety Concerns
3.6.1
When selecting the position for the installation of the boiler please comply with the following
safety requirements:
•
Ensure easy access to the components of the boiler to facilitate maintenance.
•
The room where the boiler will be placed must always be frost free.
•
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this
or any other appliance.
•
Never use or store any chlorinated detergents or halogenated hydrocarbons (e.g. in
spraycans, solvents and detergents, paints, adhesives) in proximity to the boiler.
•
For outdoor installation see
Warning for Outdoor installation
on page 16.
Products to Avoid in the Boiler Room
3.6.2
Do NOT store the following products in the boiler room and/or around combustion air intake
vents.
•
Spray cans containing chlorocarbons/fluorocarbons
•
Ammonium and/or ammonium solutions
•
Permanent wave solutions
•
Chlorinated waxes and/or cleaners
•
Chlorinated swimming pool chemicals
•
Calcium chloride used for thawing
•
Sodium chloride used for water softening
•
Refrigerant leaks
•
Paint or varnish removers
Well or Trench
for Condensate
Drain Pipe
Condensate
Drain Pipe
Boiler Housekeeping
Pad (Support Base)
At Least
3.93” (100mm)
MODULEX EXT
Boiler Front