![Aerco MODULEX EXT 1123 Скачать руководство пользователя страница 117](http://html.mh-extra.com/html/aerco/modulex-ext-1123/modulex-ext-1123_user-manual_2861553117.webp)
MODULEX EXT 321, 481, 641, 802, 962, 1123 BOILERS
Installation, Operation & Maintenance Manual
OMM-0087_0F
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
117
of
146
GF-143
Phone: 800-526-0288
07/13/15
BCM (Boiler Communications Module) Fault Codes
6.1.2
The table below lists the fault codes and troubleshooting tips associated with the BCM.
Table 6-3: BCM Fault Codes
CODE
DESCRIPTION
EFFECT
CORRECTION
RESET
E 17
Boiler pipe is frozen.
Flow sensor temp. is
36°F or less.
Ignition is
inhibited. Pump
runs for 5 min at
max speed.
Carefully
defrost boiler.
AUTOMATIC - when Flow
sensor is greater than 41°F.
E 18
Maximum Δ-
temperature protection.
Flow temperature -
Return Temperature >
Water Δ-Temp
Prot 50°F
All burners turned
OFF and Pump
ON at maximum
speed.
Check the
system
installation.
AUTOMATIC - when Δ-
temperature < Water Δ-
Temp Protection.
E 19
High outlet
temperature. Flow
sensor temperature >
203°F.
All burners turned
OFF and pump
ON at maximum
speed.
Check Flow
Sensor or
system pump.
AUTOMATIC - when Flow
sensor < 176°F.
E 37
BCM: Internal fault
E 38
Settings corrupted by
electromagnetic
interference.
Ignition is
inhibited. Pump
runs for 5 min at
max speed.
Re-program
the settings.
Contact
factory.
MANUAL - push reset
switch or cycle power.
E 56
BCM: No remote
control detected
E 57
BCM: No BMM
detected
E 58
BCM: Sensor global
flow detected.
Ignition is
inhibited.
Close request
input for
manual
operation.
MANUAL - push reset
switch or cycle power.