![Aerco Esteem 399 Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/aerco/esteem-399/esteem-399_installation-and-maintenance-instructions-manual_2861535057.webp)
57
12 - INSTALLATION - CATEGORY IV: Vent and combustion air
12.8.1 - Polypropylene air
intake connection
Combustion Air Intake connection
(see Figure 12-13 Item “M”) is used
to provide combustion air directly to
the heater from outdoors. Combustion
air piping must be supported per
guidelines listed in the National
Mechanical Code, Section 305, Table
305.4 or as local codes dictate.
To connect a polypropylene pipe to
the air intake connection proceed as
follows while referring to Figure 12-13:
1. install heater adapter “P” (Field
provided) above exit “M” using
gasket “D” and bolts “E”.
2. Insert vent pipe “N”, into adapter
“P”, following instruction of
polypropylene pipe manufacturer.
12.8.2 - Polypropylene
vent connection
Vent connection (Figure 12-13 item
“C”) is used to provide a passageway
for conveying combustion gases
to the outside. Vent piping must be
supported per the National Building
Code, Section 305, Table 305.4 or as
local codes dictate.
To connect a polypropylene pipe
to the vent connection proceed as
follows while referring to Figure 12-13:
1. install heater adapter “B” (Field
provided) above exit “C” using
gasket “D” and bolts “E”.
2. Insert vent pipe “G”, into adapter
“B”, following instruction of
polypropylene pipe manufacturer.
WARNING!!!
Do not
insulate polypropylene
exhaust pipe nor install into
an enclosure, closet, alcove or
any other obstruction thereby
preventing the cooling of the
exhaust pipe. Failure to follow
this warning could result in
excessive levels of carbon
monoxide or a fire, which can
result in severe personal injury
or death!
Figure 12-13 Polypropylene
air intake/vent connection
Figure 12-14 Polypropylene
air intake/vent connection
correctly in place
Extend the
flue exhaust
pipe to
outside
building
020010.01.016
Extend the
air intake
pipe to
outside
building
A =
VITON-BASED RTV high
temperature silicone (or
equivalent) (Field provided)
B = Flue exhaust adapter for
PVC/CPVC pipe
C = Flue exhaust connection
D = Gasket
E = Fixing screws
F = Mechanically secure clamp
G = PVC/CPVC exhaust pipe
(Field provided)
H = Combustion analization
probe (Field installed)
L = Cap (Field provided)
N = PVC/CPVC air inlet pipe
(Field provided)
P = Air intake adapter for PVC/
CPVC pipe
C
M
D
A
B
F
D
A
E
P
F
H
G
L
N
020010.01.010_PP
Combustion
air intake
Flue
exhaust
020010.01.039
CAUTION!!!
Apply a liberal
even coat of
VITON-BASED
RTV
high temperature silicone
(or equivalent) to the internal
side of the heater adapter (item
“B” and “P” fig.12-13)