114
Heater MODEL
199
250
Category of discharge chimney
II and IV
II and IV
Maximum heat input
Btu/hr
199,500
250,000
Minimum heat input
Btu/hr
50,000
50,000
Turndown ratio
4:1
5:1
Number of burners
1
1
Gas flow rate (Natural gas)
ft3/hr
199.5
250
Gas flow rate (LP gas)
ft3/hr
80
100
Min / Max gas pressure (Nat. and LP)
In.W.C.
3 / 13
3 / 13
Min / Max water temperature
°F
68 / 180
68 / 180
Min / Max water pressure
PSI
8 / 160
8 / 160
Minimum water flow
GPM
0
0
Content of water
gal
33.7
34
Supply voltage / Frequence
120Vac 60Hz
120Vac 60Hz
Absorbed electric power (pump excluded)
W
110
150
Air intake / Flue gas pipes diameter
inch
3
3
Max. length venting system
ft
120
120
CO (Carbon monoxide) with natural gas
ppm
<150
<150
CO (Carbon monoxide) with LP gas
ppm
<250
<250
NOx (0% O2 with natural gas)
ppm
<30
<30
CO2 (Carbon dioxide) for Natural gas at high fire
%
8.4 to 8.7
8.8 to 9.1
CO2 (Carbon dioxide) for Natural gas at low fire
%
8.4 to 8.7
8.8 to 9.1
CO2 (Carbon dioxide) for LP gas at high fire
%
9.5 to 10
9.5 to 10
CO2 (Carbon dioxide) for LP gas at low fire
%
10.5 to 11.5
10.5 to 11.5
O2 (Oxygen) for Natural gas at high fire
%
5.9 to 5.4
5.2 to 4.7
O2 (Oxygen) for Natural gas at low fire
%
5.9 to 5.4
5.2 to 4.7
O2 (Oxygen) for LP gas at high fire
%
6.4 to 5.6
6.4 to 5.6
O2 (Oxygen) for LP gas at low fire
%
4.8 to 3.4
4.8 to 3.4
Ionisation current
uA (Micro Amps)
4 to 7
4 to 7
Maximum flue gas temperature
°F
203
203
Maximum water condensate flow
GPM
0.032
0.039
Maximum permissible depression in flue gas system / intake
Pa
50
50
Average acidity of condensation
PH
4
4
Heater weight - Empty of water / Full of water
lb
211 / 411
216 / 428
Recovery Rating (100°F rise)
Gal/hr
227
285
DHW delivery (75°F rise)
GPM
5
6.3
18 - TECHNICAL DATA
Содержание Esteem 399
Страница 3: ...3 SAFETY INSTRUCTIONS ...
Страница 5: ...5 SAFETY INSTRUCTIONS ...
Страница 112: ...112 17 MAINTENANCE ...
Страница 116: ...116 19 SPARE PARTS Spare parts ...
Страница 135: ......