AM - R water heaters’ parameters
Ref.
Parameter’s description
Range
Factory
settings
Single burner
(mod. 199 and 250)
Burner 1 (Master)
(mod. 399 and 500)
Burner 2
(mod. 399 and 500)
Column for custom.
values
3001
Burner logic address
0 = No cascade,
1 = Burner 1 (Master),
2 to 4 = Burner 2 to 4 (slave burners)
2
1
1
2
3002 Fan speed range
0 to 4
0
199 = 0
250 = 2.
399 = 0
500 = 2.
399 = 0
500 = 2.
3003 Display units
C = °C and bar units;
F = °F and PSI units;
F
F
F
F
3004
Water pressure sensor
0 = Disabled; 1 = Enabled; 2 = N/A; 3 = N/A
1
1
1
0
3005 Burner flapper valve
0 = Disabled; 4 = Enabled; 8 = N/A; 12 = N/A;
4
0
4
4
3006
Water flow sensor
0 = Disabled; 16 = N/A; 32 = N/A; 48 = Enabled
48
48
48
48
3007 Condensate blocked drain detector
EnAb = Enabled; dISA = Disabled
Enab
Enab
Enab
dISA
3008 Flue gas detector
SEnS = Sensor; StCH = Switch
SEnS
SEnS
SEnS
SEnS
3009 Outdoor thermistor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
3010
Other thermistor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
3011
Pump MODE
0 = Local pump; 1 = N/A; 2 = N/A; 3 = N/A;
0
0
0
0
3012
DHW mode
0 = no DHW; 1 = DHW store with sensor; 2 = DHW
store with thermostat; 3 = N/A; 4 = N/A; 5 = N/A
0
0
0
0
3013
Reset Err 115
EnAb = Enabled; dISA = Disabled
Enab
Enab
Enab
Enab
3015 Reset curve design: Maximum heating supply temperature (This parameter
is overruled by 3017 parameter)
68°F to 194°F
179°F
N/A
N/A
N/A
3016
Reset curve design: Minimum heating supply temperature
68°F to 194°F
68°F
N/A
N/A
N/A
3017 Maximum supply temperature (This parameter overrule 3015 parameter)
68°F to 194°F
140°F
140°F
140°F
140°F
3018 Minimum supply temperature
68°F to 194°F
89°F
89°F
89°F
89°F
3020
Type of water flow sensor
0 = N/A; 1 = DN8; 2 = DN 10; 3 = DN 15; 4 = DN 20; 5
= DN 25
3
4
4
4
3022
Minimum water pressure
0 to 74 PSI
14
14
14
14
3035 Minimum heat exchanger water flow
0 to 26.4 GPM
7.1
7.1
7.1
7.1
3050 Number of slave burners
0 to 3
3
0
1
0
3085 Modbus address
0 to 126
1
1
1
1
3086
Number of Stopbits
1 or 2
1
1
1
1
3100 Material selection
ABS; CPVC; PVC; SST; PP.
PVC
PVC
PVC
PVC
3101 Country selection
US = United States; CA = Canada;
US
US
US
US
Switch
“S4”
Position of Switch “S4” (see Figure 17-13)
On or Off
On
On
On
Off
21 - FACTORY MENU
The heater’s micro-processor makes
this menu of parameters available to
the
qualified technician for the setting
of the appliance.
To enter this menu operate as follow:
1. turn the main electrical supply Off;
2. press and hold, in the same time,
RESET key and
q
key;
3. keeping the before mentioned
button pressed, turn the power on;
4. wait until the word “init” is displayed
or until display start to show the
3000
parameters;
5. leave before the RESET button and
after the
q
key;
6. parameters
3000
start to be
displayed;
7. press and release
q
and
p
buttons to scroll through the list of
the parameters;
8. once the parameter has been
selected, it can be changed
pressing the RESET button (value
start to blinking) and using the
q
and
p
keys you can change the
value;
9. press RESET key to save the
change;
10. wait 10 seconds;
11. turn the main electrical supply Off;
12. turn the main electrical supply On
to leave the Factory menu.