Step 3: Configure ALL C-More Units
On ALL Boilers:
1. Go to the
Configuration Menu
and set the
BST Menu
item to
Enabled
.
2. Go to the
BST Menu
and set the
BST Mode
item to
BST Slave
(for now).
On MASTER only:
3. Go to the
BST Setpoint
item and enter the Failsafe Setpoint.
4. Go to the
BST Setup Menu
item and set to
Enabled
.
5. Go to the
BST Setpoint Mode
item and select Remote
Setpoint
.
6. Go to the
BST Remote Signal
and select either
4-20ma
or
0-20ma
.
7.
Go to the
Head Temp Source
item and select
Network
.
8. Go to the
Header Temp Addr
item and
enter the Modbus Address (240).
9. Go to the
Header Temp Point
item and enter the Modbus Point (14).
When ALL C-More units have been configured:
9. Go to the
BST Menu
of the desired
Master
unit
and set the
BST Mode
item to
BST MASTER
.