![Aerco Benchmark BMK 2500 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/aerco/benchmark-bmk-2500/benchmark-bmk-2500_user-manual_2861524062.webp)
Benchmark 2500 - 3000 Boilers
CHAPTER 4 – INITIAL START-UP
Page
62
of
204
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0094_0E
03/20/2014
Ph.: 800-526-0288
GF-137
Table 4-1: Digital Alarm Switch Controls and Display
CONTROL OR
DISPLAY
MEANING
FUNCTION
LED Display
TEMP status
Displays current water temperature or
setpoint.
RST
RESET Button
Resets the unit after an alarm condition.
UP Button
Increases the displayed temperature.
DOWN Button
Decreases the displayed temperature.
SET
SET Button
Used to access and store parameters in the
unit.
Perform the following steps to check or adjust the digital alarm switch settings:
Digital Alarm Settings
1. Set the
ON/OFF
to the ON position.
2. Press the
SET
button on the Digital Alarm Switch.
SP
will appear in the display.
3. Press the
SET
button again. The current over-temperature limit value stored in memory will
be displayed. (default = 210°F).
4. If the display does not show the required over-
temperature alarm setting, press the ▲ or ▼
arrow button to change the display to the desired temperature setting.
5. Once the desired over-temperature alarm setting (210ºF) is displayed, press the
SET
button
to store the setting in memory.
6. To calibrate the offset (P1), press and hold the
SET
button for 8 seconds on the Digital
Alarm Switch. Access code value 0 should appear in the display. The switch comes from the
factory with the code set at 0. AERCO recommends that you do not change this code.
7. Press the
SET
button again to enter the code. The first parameter label (
SP
) will appear in
the display.
8.
Using the ▲ and ▼ arrow keys, select parameter P1.
9. Press
SET
to view the value stored in memory.
10.
If the desired value is not displayed, modify the setting using the ▲ and ▼ arrow keys. The
value can be changed from -10° to +10° offset. Press
SET
to enter the value and exit to the
text parameter.
11. To exit the programming mode, press the
SET
and ▼ buttons simultaneously, or simply wait
one minute and the display will automatically exit the programming mode.
12. Once the programming mode has been exited, the display will show the current outlet water
temperature of the boiler.