Ground Resistance Testers Models 6422 & 6424
39
3.5 ENVIRONMENTAL CONDITIONS
1 = Reference range, (70 to 77) °F (21 to 25) °C
2 = Operating range, (14 to 122) °F (-10 to 50) °C
3 = Storage range (without batteries), (-40 to 158) °F (-40 to 70) °C
Range for recharging of the rechargeable batteries; (32 to 104) °F (0 to 40) °C
Indoor and outdoor use
Altitude < 6500 ft (2,000 m)
Pollution degree 2
3.6 POWER SUPPLY
Model 6422:
(6) LR6 or AA disposable batteries.
Model 6424:
(6) NiMH type AA rechargeable batteries. The charging time is
approximately 6 h.
NOTE:
During charging, the instrument cannot make measurements.
All front panel buttons are disabled..
Function
Model 6422
(disposable batteries)
Model 6424
(rechargeable batteries)
Voltage / Current
> 80 h
> 50 h
Resistance
> 2500 measurements from
5 s to 100 Ω
> 2000 measurements from
5 s to 100 Ω
Ground test (3P)
> 2000 measurements from
100 Ω
> 1500 measurements from
100 Ω
Instrument off
> 1 year
> 1 year