Ground Resistance Testers Models 6422 & 6424
31
2.3.6.1 Auxiliary Rod Positioning
To ensure measurements are not distorted by interference, we recommend
repeating the measurement with the auxiliary rods placed at a different distance
and in another direction (for example rotated 90 ° from the first alignment).
If the measurements match, they are valid. If they differ significantly, they could
be influenced by factors such as ground currents or a groundwater artery. In this
case, we recommend driving the auxiliary rods deeper into the ground.
If in-line rod configuration is not possible, you can place the rods in an equilateral
triangle. To validate the measurement, move the S rod on either side of the line
H
E
.
2.3.6.2 Ground Measurement Tips
■
To avoid “cross-talk” with the measurement current, do not route the
connecting cables of the rods near or parallel to other cables (transmission
or power supply), metal pipes, rails, or fences.
■
To reduce auxiliary rod resistance, add one or more rods, two meters apart,
in the H (S) circuit of the circuit.
■
Another way to reduce rod resistance is to drive the rods deeper and firmly
pack the earth around them, or sprinkle water on them.
NOTE:
After completing the measurement, reconnect the grounding
strip before restoring power to the installation.