32
Ground Resistance Testers Models 6422 & 6424
2.3.7 Error Messages
> 3.000 kΩ
(Model 6422) Measurement outside range
> 60.00 kΩ
(Model 6424) Measurement outside range
S
(blinking)
P
(blinking)
S rod resistance > 50 kΩ
RH !
(blinking)
H rod resistance > 15 kΩ
NOISE
U
SE
or U
HE
voltage amplitude is between 3 and 50 V
(blinking)
U
SE
or U
HE
> 50 V (no measurement is possible)
2.4 AC CURRENT MEASUREMENT (MODEL 6424)
AC current measurement requires an optional MN72 current probe.
1. Turn ON the instrument by pressing
for > 2 seconds.
2. Press
.
3. Connect the clamp to the instrument’s current terminal (identified
by the
symbol). The
A
and
symbols appear o.n the LCD.
4. Open the clamp and place it on the conductor under test.