5 Use and Operation
64
Generally, charge and discharge the battery once every 4 to 6 months. Discharge the
battery till under-voltage and power off and then charge it. In high temperature area,
charge and discharge the battery once every 2 months. The charging time for the
standard battery should be more than 10 hours every time.
If the UPS hasn't been used for a long time, it is recommended to charge the battery
more than 10 hours every three months.
Generally, the working life of battery is 3 to 5 years. If battery is not so good, replace it in
time. The battery replacement should be performed by authorized professional.
5.7 Troubleshooting
5.7.1 Common Fault
As shown in Table5-1, it only includes some common fault diagnosis. If any doubt, contact
the local office or distributor for details.
Table5-1
Troubleshooting
Fault phenomenon
Possible reason
The mains normal, after
starting the UPS, it outputs
normally, but it works in the
battery mode and the buzzer
beeps intermittently.
1.
Check if the contactors and wiring terminals in the input
circuit are in good condition;
2.
Check if the displayed input voltage amplitude or
frequency of mains on the LCD is beyond the allowable
range of UPS;
3.
Check if the mains input breaker is disconnected, if yes,
please close the breaker again.
After installing UPS,
connecting with power will
fuse the fuse or cause
tripping operation.
The wiring of UPS input or output is short circuit.
After starting, the LCD
display and output are
normal. But once connecting
with load, it will stop
outputting immediately.
1.
UPS is overload seriously or the output circuit is
short-circuit. Please reduce load to proper capacity or
find the short-circuit reason. The common reason is
that the output changeover socket short-circuit or the
input short-circuit after UPS damage;
Содержание IST9
Страница 1: ...l un I Jet _________ __ AEC IST9 1 0 20 https www uni jet com catalog ibp on line ibp aec ist9...
Страница 2: ...UPS IST9 10 20 kVA User Manual...
Страница 3: ......
Страница 9: ......
Страница 52: ...3 Installation 43 Figure3 29 Diagram of 33 mode parallel system wiring of 10kVA 20kVA UPS...
Страница 53: ...3 Installation 44 Figure3 30 Diagram of 31 mode parallel system wiring of 10kVA 20kVA UPS 30kVA 40kVA...
Страница 54: ...3 Installation 45 Figure3 31 Diagram of 33 mode parallel system wiring of 30kVA 40kVA UPS...
Страница 82: ......