A Technical Specifications
71
Model
Index
10kVA
15kVA
20kVA
30kVA
40kVA
Battery
voltage (Vdc)
±144~±240 (can be selected from ±12 cells ~±20 cells, default is ±16 cells, when
the battery voltage is set from ±12 cells ~±15 cells, the output of the UPS
decreases to 75% rated) (single battery voltage is 12Vdc)
Charge
current (A)
1~10 settable (default is 4A)
1~20 settable (default is 15A)
O
u
tp
u
t
Output mode 3W+N+PE(can be set to 1W+N+PE)
Capacity
(kVA/kW)
10/9
15/13.5
20/18
30/27
40/36
Voltage (Vac)
L-N: 220/230/240(default is 220)
L-L: 380/400/415 (default is 380)
Frequency
(Hz)
When mains normal, it tracks the bypass input frequency;
When mains abnormal, it tracks the frequency of 50±0.1 or 60±0.1 (default is 50)
Wave form
Sine-wave
Voltage
distortion
Resistive full load: ≤1%; non-linear full load:≤4%
Power factor
0.9(when PF set to 1.0, the UPS can output long time)
Transfer time
of
bypass
and inverter
(ms)
Synchronization:
<
1ms; asynchronization:
<
10ms
System
efficiency
Up to 96%
Overload
capacity
Inverter:
<115
%
: continue
115
%
~130
%
: 15min
Содержание IST9
Страница 1: ...l un I Jet _________ __ AEC IST9 1 0 20 https www uni jet com catalog ibp on line ibp aec ist9...
Страница 2: ...UPS IST9 10 20 kVA User Manual...
Страница 3: ......
Страница 9: ......
Страница 52: ...3 Installation 43 Figure3 29 Diagram of 33 mode parallel system wiring of 10kVA 20kVA UPS...
Страница 53: ...3 Installation 44 Figure3 30 Diagram of 31 mode parallel system wiring of 10kVA 20kVA UPS 30kVA 40kVA...
Страница 54: ...3 Installation 45 Figure3 31 Diagram of 33 mode parallel system wiring of 30kVA 40kVA UPS...
Страница 82: ......