3 Installation
IST6
Series (200K-600K) Modular UPS
User Manual
34
All rights reserved ©
Allis Electric
Co., Ltd.
Table3-1
Recommended wire and terminal specification (The power of single power module is 50kVA)
Model
System max. capacity (kVA)
200
300
400
500
600
A
C
i
nput
AC input current (A)
349
523
697
871
1045
Recommended
wire diameter
(mm
2
)
U/V/W/N
2
×
(4
×
95)
2
×
(4
×
120)
2
×
(4
×
185)
2
×
(4
×
240)
3
×
(4
×
240)
Wire terminal model
DT-95
DT-120
DT-185
DT-240
DT-240
B
ypas
s i
np
ut
Bypass input current (A)
303
455
606
758
909
Recommended
wire diameter
(mm
2
)
U/V/W/N
2
×
(4
×
70)
2
×
(4
×
95)
2
×
(4
×
150)
2
×
(4
×
185
3
×
(4
×
240)
Wire terminal model
DT-70
DT-95
DT-150
DT-185
DT-240
O
ut
put
Output current (A)
303
455
606
758
909
Recommen
ded wire
diameter
(mm
2
)
U/V/W/N
(for non-linear load, it
needs to increase the
wire diameter of
neutral wire)
2
×
(4
×
70)
2
×
(4
×
95)
2
×
(4
×
150)
2
×
(4
×
185)
3
×
(4
×
240)
Wire terminal model
DT-70
DT-95
DT-150
DT-185
DT-240
B
at
ter
y i
nput
Nominal discharge current of storage
battery (the current of equipped
±
20 pieces of 12V storage (480V))(A)
443
664
886
1107
1329
Max. discharge current of storage
battery (the ending discharge current
value <the voltage of each battery is
10.5V> for equipped
±
20 of 12V
storage)(A)
506
759
1012
1265
1518
Содержание IST6
Страница 1: ...UPS IST6 200 600kVA Series User Manual www aecups com ...
Страница 123: ......