IST6
Series (200K-600K) Modular UPS
User Manual
2 Overview
All rights reserved ©
Allis Electric
Co., Ltd.
21
1--8
RJ45
plug
RJ45
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Pin definition
:
Pin 1
:
White orange-Reserved
Pin 2
:
Orange-Reserved
Pin 3
:
White green-MODBUS:A
Pin 4
:
Blue-MODBUS:B
Pin 5
:
White blue-MODBUS:A
Pin 6
:
Green-MODBUS:B
Pin 7
:
White brown-Reserved
Pin 8
:
Brown-Reserved
Figure2-16
Pin definition of MODBUS/RS485 port
Output dry contact
Table2-6
Function illustration for output dry contact
NO. Silk-screen Signal
Function description
1
ND1
UPS FAULT
signal
When the signal valid, COM and NO is closed, COM and
NC is opened. Allowable withstand voltage is 250V/1A. The
signal is preset and cannot set.
2
ND2
LINE
FAIL
signal
When the signal valid, COM and NO is closed, COM and
NC is opened. Allowable withstand voltage is 250V/1A. The
signal is preset and cannot set.
3
ND3
BAT. LOW or
start generator
signal
When the signal valid, COM and NO is closed, COM and
NC is opened. Allowable withstand voltage is 250V/1A. The
signal can be set to battery low-voltage or start generator,
default is battery low-voltage.
4
ND4
Bypass
fault
or
output
overload
signal
When the signal valid, COM and NO is closed, COM and
NC is opened. Allowable withstand voltage is 250V/1A. The
signal can be set to bypass fault or output overload, default
is bypass fault.
Input dry contact
Table2-7
Function illustration for input dry contact
NO. Silk-screen Signal
Function description
1
ND5
External
When NC and COM is short-circuit, the signal is valid. The