2 Overview
IST6
Series (200K-600K) Modular UPS
User Manual
18
All rights reserved ©
Allis Electric
Co., Ltd.
NO.
Name
Illustration
○
4
Ready switch
Place the ready switch to “unlock” status, the indication
color is green, the bypass module is not locked with the
cabinet, and at this time, the bypass module can be
dismantled.
Place the ready switch to “lock” status, the indication color
is red, the bypass module is locked with the cabinet, and at
this time, the bypass module cannot be dismantled.
○
5
Battery start button
At the status of no mains, bypass, press the button for 2s, the
system will start from battery status.
2.4.4 System Control Box
The system control box unit is as shown in Figure2-12.
Figure2-12
System control box unit
System control card
Figure2-13
System control card
Table2-4
Illustration for system control card
NO.
Name
Illustration
○
1
BSC port
The output double bus control port is used in double bus