PCI-1241/1242 User Manual
82
C.5 Home Mode3
In Home mode3, the motor will start up at low speed FL, and accelerate
to high speed FH towards the home sensor. Once the home sensor is
reached, the motor starts to search for an encoder index signal with high
speed FH. After the index is reached, the motor will decelerate to FL then
stop. Meanwhile, you can configure how many index counts will be
ignored with parameter “EIC”. When EIC is ‘1’, this means one index
will be ignored and the motor will stop at the second index after the home
sensor was triggered. Like case 1 in following diagram.
If the home sensor was active at start up, or the limit switch was met first,
the motor will go in the opposite direction when reaching the limit switch.
Then it will keep moving until it crosses the home sensor, and finally
search the home signal again. Like case 3 and case 4 in figure 4-4.
Figure C.4: Velocity Profile of Home Mode3
HOME
LMT
Case 2
(EIC=2)
Case 1
(EIC=1)
ECZ
Case 4
Case 3
(EIC=1)
(EIC=1)