APAX-5000 I/O User Manual

34

Configure Different Range for Each Channel:

 Yes

Resolution:

Sampling Rate:

 12 samples/second (total)

CMR @ 50/60 Hz: 

90 dB

NMR @ 50/60 Hz:

 67 dB

Noise Suppression for Frequency:

 Hardware Filter (50/60 Hz)

Span Drift:

 ±25 ppm/

 C

Zero Drift:

 ±6 

V/

 C

Thermocouple Wire Burn-out Detection:

 Yes 

(When the loop resistance > 1K

, it will detect as wire burn-out)

Input Characteristic Curve:

 According to IEC 61131-2

Common Mode Voltage:

 up to 200 VDC

Wire Burnout Detection:

 For 4 ~ 20 mA range and all thermocouple type

Protection

Isolation:

 2,500 VDC (Between channels and backplane bus)

Note!

This accuracy information only relates to the operating error, not includ-
ing cold connection CJC error. The CJC error can  be eliminated by per-
forming CJC compensation. 

Voltage

Range

Resolution

±50 mV

16 bit

±100 mV

16 bit

±250 mV

16 bit

±500 mV

16 bit

±1 V

16 bit

±2.5 V

16 bit

Current

Range

Resolution

±20 mA

15 bit

0 ~ 20 mA

14 bit

4 ~ 20 mA

14 bit

Thermocouple

Range

Resolution

Type J

14 bit

Type K

14 bit

Type T

15 bit

Type E

15 bit

Type R

14 bit

Type S

14 bit

Type B

14 bit

Содержание APAX-5013

Страница 1: ...User Manual APAX 5000 Series I O Modules...

Страница 2: ...ation Advantech assumes no liability under the terms of this warranty as a consequence of such events Because of Advantech s high quality control standards and rigorous testing most of our customers n...

Страница 3: ...ire Pro tection Association work sites are classified into different classes divisions and groups based on hazard considerations This equipment is compliant with the speci fications of Class I Divisio...

Страница 4: ...t overvoltage 13 Never pour any liquid into an opening This may cause fire or electrical shock 14 Never open the equipment For safety reasons the equipment should be opened only by qualified service p...

Страница 5: ...1 2 1 4 APAX 5018 12 ch Thermocouple Input Module 32 Figure 2 7 APAX 5018 Module Front View 32 Figure 2 8 Wiring for APAX 5018 33 2 1 5 APAX 5017PE 12 ch Analog Input Module for P E Applications 36 Fi...

Страница 6: ...ce 75 Figure 3 32A B Phase 2X With Reload Count Repetitively 76 Figure 3 33A B Phase 4X No Reload Count Once 77 Figure 3 34A B Phase 4X With Reload Count Once 78 Figure 3 35A B Phase 4X With Reload Co...

Страница 7: ...es 102 3 4 1 APAX 5090P 4 port RS 232 422 485 Communication Module 102 Figure 3 58APAX 5090P Module Front View 102 Figure 3 59APAX 5090P Function Block Diagram 102 Table 3 1 Configuration Settings 103...

Страница 8: ...APAX 5000 I O Series User Manual viii...

Страница 9: ...Chapter 1 1 Overview...

Страница 10: ...tions Analog I O APAX 5013 8 ch RTD Module APAX 5017 12 ch Analog Input Module APAX 5018 12 ch Thermocouple Input Module APAX 5017H 12 ch High Speed Analog Input Module APAX 5028 8 ch Analog Output Mo...

Страница 11: ...type terminal blocks clamp type terminal blocks can save up to 75 wiring time and provide better reliability for shock and vibration Follow the pro cedures below for wiring your APAX 5000 I O module...

Страница 12: ...ock Warning APAX 5000 I O modules can be categorized into four categories AI AO DI and DO If you insert a terminal block into a module which has a different function it might damage the modules for ex...

Страница 13: ...ntech provides write on labels for each APAX 5000 I O module This write on label has two sides one with the model name specifications and a wiring diagram while the other side allows users to write in...

Страница 14: ...through the onboard jumpers This section will show you how to adjust the jumper settings 1 Pull out the write on label and you can see the location of the jumper 2 You can use the screw driver to adj...

Страница 15: ...t side Rotate that ID switch and point the hole on the central axis to correspond ing ID number 0 F Refer to figures below for the location of the rotary ID switch and how to set the ID number by the...

Страница 16: ...n the PCB that it can double the available ID number Thus the maximum number for digital module in one system is 32 You can distinguish if the ID number is doubled by the front LED When the LED color...

Страница 17: ...swich Green Warning Avoid two modules with the same ID number in the same system or you cannot see the module in the software utility The LED on the front side will flash four times if two or more mo...

Страница 18: ...between backplanes and provides to all APAX 5000 I O modules inserted on the backplanes Refer to figures below for how to wiring the power to the backplane and how to assembly APAX 5000 I O modules w...

Страница 19: ...O module to the APAX 5002 backplane by pulling down the module locks 4 Insert another APAX 5000 I O module on the same APAX 5002 backplane Use tongue and groove slots to move the module 5 Lock that AP...

Страница 20: ...ackplane locks Warning When you assembly different backplanes together remember to turn off the power connected to the backplane If not the backplanes may be damaged Turn on the power again after you...

Страница 21: ...module locks similar as step 5 10 If needed repeat step 8 9 to have another APAX 5000 I O module on the same APAX 5002 backplane If you need more APAX 5000 I O module repeat Step 6 Step 10 until all n...

Страница 22: ...s though the backplanes 1 Follow the procedure described in Section 1 7 1 to assembly APAX 5000 I O modules into one complete system The only difference is that you don t need to connect the power sup...

Страница 23: ...15 APAX 5000 I O Series User Manual Chapter 1 Overview...

Страница 24: ...side of the first APAX 5002 back plane in the system 4 Lock the stacked APAX 5343E backplane with the APAX 5002 backplane by the backplane locks on the APAX 5002 backplane 5 Insert the upper case of...

Страница 25: ...serted on the backplane when the complete sys tem is power on This can significantly help to make it more convenient for system maintenance Changing one module won t affect operation of other modules...

Страница 26: ...ule locks to lock on the backplane and APAX 5000 I O module will be power on and can be used The device must be fully dismantled in order to dispose of it Electronic parts must be disposed of in accor...

Страница 27: ...f all backplanes into the position to fix all backplanes to the DIN rail 6 Insert all necessary APAX 5000 I O modules to the backplanes Similar to Step 2 Step 4 and Step 8 in section 1 7 1 7 Slide the...

Страница 28: ...0 I O module to a wall panel through backplane using two screws per module Use M4 or 8 panhead screws Refer to figure below for the dimensional template Below are the procedures for the wall panel mou...

Страница 29: ...rew for APAX 5002 to hang should be special designed We have provided it in accessory Diameter 9 mm length 16 mm height of head 2 7 mm 3 Mount the first APAX 5002 backplane to the wall panel using two...

Страница 30: ...Series User Manual 22 4 Stack Another APAX 5002 backplane to original backplane Lock the two back planes together 5 Mount the second APAX 5002 backplane to the wall panel using two standard M4 or 8 p...

Страница 31: ...1 7 1 8 Lock APAX 5520 and all necessary APAX 5000 I O module to the backplane by pull down the buckle Similar to Step 3 Step 5 and Step 9 in section 1 7 1 Note When the total number of APAX 5000 I O...

Страница 32: ...ies User Manual 24 We suggest remaining enough clearance space from enclosure walls and adjacent equipments Allow 50 mm 2 in of space on all sides as shown below This provide ventilation and makes ass...

Страница 33: ...Chapter 2 2 Analog Input Output Modules...

Страница 34: ...transformer based isolation up to 2 500 VDC 2 1 1 APAX 5013 8 ch RTD Module The APAX 5013 is a 16 bit 8 channel RTD input module that features programmable input ranges on all channels This module is...

Страница 35: ...rent Range for Each Channel Yes Resolution 16 bit Accuracy 0 1 of FSR at 25 C Sampling Rate 50 Hz filter 8 sample second total 60 Hz filter 10 sample second total CMR 50 60 Hz 90 dBs NMR 50 60 Hz 60 d...

Страница 36: ...input Refer to the figure below to see how to define the input type by the jumper Besides you can use software APAX utility to configure range type for each channel This module is an extremely cost ef...

Страница 37: ...ft 30 ppm C Zero Drift 6 V C Input Characteristic Curve According to IEC 61131 2 Common Mode Voltage up to 200 VDC Wire Burnout Detection Only for 4 20 mA range Note To keep measurement accuracy pleas...

Страница 38: ...ut Module APAX 5017H is an 12 ch analog differential input module that provides programma ble input ranges on each channel Its sampling rate depends on the data format received up to 1000 sample secon...

Страница 39: ...Span Drift 25 ppm C Zero Drift 6 V C Input Characteristic Curve According to IEC 61131 2 Wire Burnout Detection Only for 4 20 mA range Protection Over Voltage Protection 35 VDC Isolation 2 500 VDC Bet...

Страница 40: ...current input 20 mA 0 20mA 4 20mA and thermocouple input Type J K T R S E B An external CJC on the plug in ter minal is designed for accurate temperature measurement The module provides 2500 VDC optic...

Страница 41: ...25 C Temperature Range and Accuracy Note You can use the jumpers to configure each analog input channel type voltage thermocouple or current Refer to Section 1 5 for the location of the jumpers There...

Страница 42: ...ltage up to 200 VDC Wire Burnout Detection For 4 20 mA range and all thermocouple type Protection Isolation 2 500 VDC Between channels and backplane bus Note This accuracy information only relates to...

Страница 43: ...ut Output Modules Environment Operating Temperature 10 60 C when mounted vertically Storage Temperature 40 70 C Relative Humidity 5 95 non condensing General Dimensions W x H x D 30 x 139 x 100 mm Wei...

Страница 44: ...hannel This module is an IEC 61850 3 compliant I O modules and suitable for measurement and monitoring for power and energy related application The highly anti electromagnetic interfer ence make it mo...

Страница 45: ...olution Sampling Rate 12 samples second total CMR 50 60 Hz 90 dB NMR 50 60 Hz 67 dB Noise Suppression for Frequency 50 60 Hz Span Drift 30 ppm C Zero Drift 6 V C Input Characteristic Curve According t...

Страница 46: ...Environment Operating Temperature 20 70 C when mounted vertically Storage Temperature 40 85 C Relative Humidity 5 95 non condensing General Dimensions W x H x D 30 x 139 x 100 mm Weight 170 g Power C...

Страница 47: ...h the configuration software For each channel voltage and current can be used by connecting to different terminal The module provides 2500 VDC optical isolation between channels and backplane bus If a...

Страница 48: ...t 250 V C Load Voltage 1000 minimum Current 0 500 Protection Isolation 2 500 VDC Between channels and backplane bus Short Circuit Protection Fail Safe Protection When I O module lose its communication...

Страница 49: ...Chapter 3 3 Digital Input Output Modules...

Страница 50: ...proximity switches The digital input channels offer LED to indicate digital status The module provides 2500 VDC optical isolation between channels and backplane bus If any high voltage or current dam...

Страница 51: ...mA At signal 1 Maximum Input Current 7 3 mA Input Filter 3 ms Input Characteristic Curve According to IEC 61131 2 type 1 Protection Isolation 2 500 VDC Between channels and backplane bus Over Voltage...

Страница 52: ...ls can generate discrete signal to external devices and change its output value to control the devices The digital output channels offer short circuit protection and LED to indicate digital status The...

Страница 53: ...k Source Wet Contact Input Voltage Rated Value 24 VDC For 0 signal 5 5 VDC For 1 signal 15 30 VDC and 15 30 VDC Input Impedance 5 4 k Input Current typical 4 4 mA At signal 1 Input Filter 3 ms Input C...

Страница 54: ...Protection Isolation 2 500 VDC Between channels and backplane bus Over Voltage Protection 70 VDC for DI channel Short Circuit Protection For DO channel Thermal Shutdown Protection For DO channel Fail...

Страница 55: ...and backplane bus If any high voltage or current damage the channels the whole system backplanes other mod ules and control unit won t be affected because it is already isolated Figure 3 5 APAX 5046...

Страница 56: ...ad max 200 Hz Using 5W lamp and testing under 24 V Protection Isolation 2 500 VDC Between channels and backplane bus Short Circuit Protection Thermal Shutdown Protection Fail Safe Protection When I O...

Страница 57: ...l status This module is an IEC 61850 3 compliant I O modules and suitable for power and energy related applica tion The highly anti electromagnetic interference make it more robust and reliable to sur...

Страница 58: ...ent 4 4 mA At signal 1 Maximum Input Current 7 3 mA Input Filter 3 ms Input Characteristic Curve According to IEC 61131 2 type 1 Protection Isolation 2 500 VDC Between channels and backplane bus Over...

Страница 59: ...urrent damage the channels the whole system backplanes other modules and control unit won t be affected because it is already isolated The APAX 5046SO supports two independent power sources with diffe...

Страница 60: ...ad max 200 Hz Using 5W lamp and testing under 24 V Protection Isolation 2 500 VDC Between channels and backplane bus Short Circuit Protection Thermal Shutdown Protection Fail Safe Protection When I O...

Страница 61: ...ches can be used to control the relays The digital output channels offer short circuit protec tion and LED to indicate digital status The module provides 2500 VDC optical isolation between channels an...

Страница 62: ...User Manual 54 Application Wiring Figure 3 12 Wiring for APAX 5060 Warning When you connect DO channel with inductive load we suggest adding one diode in the circuit to protect the APAX 5060 module Re...

Страница 63: ...esistance 30 m maximum Insulation Resistance 1 G minimum at 500 VDC Operating Time 10 ms maximum at rated voltage excluding bounce time Release Time 5 ms maximum at rated voltage excluding bounce time...

Страница 64: ...ompliant I O modules and suitable for power and energy related application The highly anti electro magnetic interference make it more robust and reliable to survive in the hush environ ment The module...

Страница 65: ...Resistance 30 m maximum Insulation Resistance 1 G minimum at 500 VDC Operating Time 10 ms maximum at rated voltage excluding bounce time Release Time 5 ms maximum at rated voltage excluding bounce tim...

Страница 66: ...APAX 5000 I O Series User Manual 58 Dimensions W x H x D 30 x 139 x 100 mm Weight 195 g Power Consumption 2 W 24 VDC typical Status Display LED per channel On Logic level 1 Off Logic level 0...

Страница 67: ...tput function the APAX 5080 supports 4 general isolated digital output and spe cific alarm function with counter For counter frequency function the APAX 5080 can support many modes of counter input ty...

Страница 68: ...APAX 5000 I O Series User Manual 60 Application Wiring Figure 3 16 Wiring for APAX 5080 Warning Please use different power supply modules for digital channels and sys tem to ensure isolation effect...

Страница 69: ...61 APAX 5000 I O Series User Manual Chapter 3 Digital Input Output Modules APAX 5080 Function Block...

Страница 70: ...irection Up Down Up Pulse A B phase and Frequency Channels 4 Pulse and Direction Up Down and A B phase mode 8 Up Pulse and Frequency mode Counting Range 32 bit 1 bit overflow underflow Minimum Pulse W...

Страница 71: ...umber of steps will be added by one and vice versa A B Phase 2X counter mode A B Phase x 2 A B Phase 4X counter mode A B Phase x 4 With Reload When the counter0 value is overflow the value will be res...

Страница 72: ...0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting Figure 3 18 Pulse DIR With Reload Count Once 0x33 0x32 0x31 Up Down...

Страница 73: ...function When the counter0 is enabled the couner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively Figure 3 19...

Страница 74: ...e counter0 is enabled the couner0 starts to count If the counter value is overflow or underflow it will show the minimum 0x00 or maximum 0xFFFFFFFF value and not count continuously Figure 3 20 Up Down...

Страница 75: ...ne pulse one down count When the counter0 is enabled the couner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting Figur...

Страница 76: ...ount When the counter0 is enabled the couner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively Figure 3 22 Up Do...

Страница 77: ...ter up mode Ch0_A provides the counting up function one pulse one up count When the counter0 is enabled the couner0 starts to count If the counter value is overflow or underflow it will reset to the d...

Страница 78: ...etitively Figure 3 25 Up With Reload Count Repetitively Frequency Figure 3 12 shows the frequency function Every counter channel can measure the frequency of assigned time window and the range is from...

Страница 79: ...ed the couner0 starts to count If the counter value is overflow or underflow it will show the minimum 0x00 or maximum 0xFFFFFFFF value and not count continuously Figure 3 27 A B Phase 1X No Reload Cou...

Страница 80: ...ouner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting Figure 3 28 A B Phase 1X With Reload Count Once 0x33 0x34 0x35...

Страница 81: ...s enabled the couner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively Figure 3 29 A B Phase 1X With Reload Coun...

Страница 82: ...uner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting Figure 3 30 A B Phase 2X No Reload Count Once 0x33 0x32 0x31 0x3...

Страница 83: ...0 is enabled the couner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively Figure 3 31 A B Phase 2X With Reload C...

Страница 84: ...s to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively Figure 3 32 A B Phase 2X With Reload Count Repetitively 0x33 0x34 0x...

Страница 85: ...arts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting Figure 3 33 A B Phase 4X No Reload Count Once 0x33 0x00 Ch0_A Ch0_B Coun...

Страница 86: ...counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively Figure 3 34 A B Phase 4X With Reload Count Once 0x33 0x33 Ch0_A Ch0_B Counter0 Value...

Страница 87: ...n trigger the counter to count once Retriggerable It means DI0 can trigger the counter to count anytime High level the DI0 trigger level Low level the DI0 trigger level Rising Edge the DI0 trigger edg...

Страница 88: ...count If the counter value is overflow or underflow it will show the minimum 0x00 or maximum 0xFFFFFFFF value and not count continuously Whatever the DI value is the counter still continu ously count...

Страница 89: ...nabled the couner0 starts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting Whatever the DI value is the counter still continuo...

Страница 90: ...alue is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting If the DI0 value is high level the counter0 will starts to count but cannot retriggered Otherwise the...

Страница 91: ...nt If the counter value is overflow or underflow t will reset to the defined value e g 0x33 but won t keep counting If the DI0 value is high level the counter0 will starts to count but cannot retrigge...

Страница 92: ...s overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 value is high level the counter0 will starts to count and can be retriggered Otherwise the...

Страница 93: ...counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 value is high level the counter0 will starts to count and can be retrigger...

Страница 94: ...ue is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting If the DI0 value is low level the counter0 will starts to count but cannot retriggered Otherwise the cou...

Страница 95: ...t If the counter value is overflow or underflow t will reset to the defined value e g 0x33 but won t keep counting If the DI0 value is low level the counter0 will start to count but cannot be retrigge...

Страница 96: ...value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 value is low level the counter0 will starts to count and can be retriggered Otherwi...

Страница 97: ...e counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 value is low level the counter0 will starts to count and can be retrigger...

Страница 98: ...lue is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting If the DI0 status is rising edge the counter0 will starts to count but cannot retriggered Otherwise the...

Страница 99: ...If the counter value is overflow or underflow t will reset to the defined value e g 0x33 but won t keep counting If the DI0 status is rising edge the counter0 will start to count but cannot be retrig...

Страница 100: ...alue is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 status is rising edge the counter0 will starts to count and can be retriggered Other...

Страница 101: ...counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 status is rising edge the counter0 will starts to count and can be retrigge...

Страница 102: ...ue is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting If the DI0 status is falling edge the counter0 will starts to count but cannot retriggered Otherwise the...

Страница 103: ...t If the counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting If the DI0 status is falling edge the counter0 will start to count but cannot be retrig ge...

Страница 104: ...lue is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 status is falling edge the counter0 will starts to count and can be retriggered Other...

Страница 105: ...ounter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting repetitively If the DI0 status is falling edge the counter0 will starts to count and can be retrigge...

Страница 106: ...t If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting If the DI0 status is rising edge the counter0 will starts to count and won t be retr...

Страница 107: ...arts to count If the counter value is overflow or underflow it will reset to the defined value e g 0x33 and keep counting If the DI0 status is rising edge the counter0 will starts to count and won t b...

Страница 108: ...t If the counter value is overflow or underflow it will reset to the defined value e g 0x33 but won t keep counting If the DI0 status is falling edge the counter0 will starts to count and won t be ret...

Страница 109: ...ill be high and when the counter value counts to defined alarm value the DO status will change high to low No Auto Reload When the counter is overflow or underflow the value will be reset to the initi...

Страница 110: ...rated with the APAX 557X series and transmits data to through the COM port The integrated sys tem is an intelligent stand alone system and can connect and issue commands to control devices such as pri...

Страница 111: ...als TxD RxD RTS CTS GND for RS 232 TxD RxD TxD RxD for RS 422 Data Data for RS 485 Isolation 2500 VDC Connector PLUG_26_3 81mm NONE jumper change mode Environment Operating Temperature 10 70 C when mo...

Страница 112: ...tection with an automatic transmission repeat function This drastically reduces the chance of data loss and ensures system reliability The on board CAN controllers are located at different positions i...

Страница 113: ...dware Communication Controller SJA 1000 CAN Transceiver 82C250 Signal Support CAN_H CAN_L Speed bps Up to 1 Mbps programmable transfer rate Isolation Protection 2000 VDC Connector DB9 Operating Temper...

Страница 114: ...ts data to through the COM port The integrated system is an intelligent stand alone system and can connect and issue commands to control devices such as print ers and PLCs in remote factory location F...

Страница 115: ...C when mounted vertically Relative Humidity 5 95 Storage Temperature 40 70 C non condensing Configuration Settings SW4 COM1 SW5 COM2 SW6 COM3 SW7 COM4 SW4 7 Status Function PIN1 ON Force Disable RS 23...

Страница 116: ...APAX 5000 I O Series User Manual 108...

Страница 117: ...Chapter 4 4 Backplane Modules...

Страница 118: ...lso be used between two APAX 5002 Therefore you can flexibly build any remote expansion with line tree or star topology All the APAX 5000 I O modules can benefit from the remote expansion architecture...

Страница 119: ...neral Dimensions W x H x D 28 x 151 x 38 mm Weight 70 g Mounting DIN rail wall panel Power Input 24 VDC Power Consumption 0 3 W 24 VDC 4 3 APAX 5004L 4 slot Backplane Module APAX 5004L is an interface...

Страница 120: ...APAX 5000 I O Series User Manual 112...

Страница 121: ...Chapter 5 5 Power Supply Modules...

Страница 122: ...l 60 ms Rated Output Current 3 A Output Current Limitation 3 5 4 3 A Efficiency 87 at 115 230 VAC Input Voltage Rated load Protection Isolation Protection In Out 42 42 VDC Over Voltage Protection Shut...

Страница 123: ...stability especially in the envi ronment with high electromagnetic interference such as power substation And this is a necessary unit for APAX to complaint with the IEC 61850 3 standard APAX 5350 Spe...

Страница 124: ...APAX 5000 I O Series User Manual 116...

Страница 125: ...Chapter 6 6 Error Handling and Diagnostics...

Страница 126: ...tself Solution 1 Download latest firmware again to see if it works well 2 If the LED continues flashing after updating firmware then you need to contact Advantech for technical support LED continues f...

Страница 127: ...I O module Solution 1 Check ID number of all I O modules in the same system Adjust the ID number to avoid different I O modules with the same ID number Refer to Section 1 6 for how to adjust ID numbe...

Страница 128: ...APAX 5000 I O Series User Manual 120...

Отзывы: