Figure 2.8 Wiring for APAX-5018
APAX-5018 Specifications
Channels:
12 (Differential)
Input Type:
V, mV, mA, Thermocouple
Voltage/Current Range:
±50mV, ±100mV, ±500mV, ±1V, ±2.5V, ±20mA, 0~20mA, 4~20 mA
Voltage and Current Accuracy:
±0.1% or better (Voltage), ±0.2% or better
(Current) at 25
C
Temperature Range and Accuracy:
Note!
You can use the jumpers to configure each analog input channel type
(voltage/thermocouple or current). Refer to Section 1.5 for the location
of the jumpers. There are a total of 12 jumpers and each is specific for
one channel.
Type
Range
Accuracy
Type J
-210 ~ -150 ° C
±2.5 ° C
-150 ~ 1200 ° C
±2 ° C
Type K
-230 ~ -150 ° C
±4 ° C
-150 ~ 1372 ° C
±2.5° C
Type T
-230 ~ -150 ° C
±2° C
-150 ~ 400 ° C
±1.5 ° C
Type E
-230 ~ -150 ° C
±2.5 ° C
-150 ~ 1000 ° C
±2 ° C
Type R
0 ~ 100 ° C
±2.5° C
100 ~ 1768 ° C
±2 ° C
Type S
0 ~ 100 ° C
±2.5 ° C
100 ~ 1768 ° C
±2 ° C
Type B
200 ~ 400 ° C
±4 ° C
400 ~ 1820 ° C
±3 ° C
Содержание APAX-5013
Страница 1: ...User Manual APAX 5000 Series I O Modules...
Страница 8: ...APAX 5000 I O Series User Manual viii...
Страница 9: ...Chapter 1 1 Overview...
Страница 23: ...15 APAX 5000 I O Series User Manual Chapter 1 Overview...
Страница 33: ...Chapter 2 2 Analog Input Output Modules...
Страница 49: ...Chapter 3 3 Digital Input Output Modules...
Страница 69: ...61 APAX 5000 I O Series User Manual Chapter 3 Digital Input Output Modules APAX 5080 Function Block...
Страница 116: ...APAX 5000 I O Series User Manual 108...
Страница 117: ...Chapter 4 4 Backplane Modules...
Страница 120: ...APAX 5000 I O Series User Manual 112...
Страница 121: ...Chapter 5 5 Power Supply Modules...
Страница 124: ...APAX 5000 I O Series User Manual 116...
Страница 125: ...Chapter 6 6 Error Handling and Diagnostics...
Страница 128: ...APAX 5000 I O Series User Manual 120...