71
APAX-5000 I/O Series User Manual
Chapter 3
D
igital Input
/Output
Modules
A/B Phase 1X, No Reload, Count Once
Figure 3.13 shows A/B Phase 1X mode, Ch0_A and Ch0_B provide the counting
function. When the counter0 is enabled, the couner0 starts to count. If the counter
value is overflow or underflow, it will show the minimum (0x00) or maximum
(0xFFFFFFFF) value and not count continuously.
Figure 3.27 A/B Phase 1X, No Reload, Count Once
0x33
0x34
0x35
0x34
0x33
0x32
………
0x00
0xFFFFFFFF
Ch0_A
Ch0_B
Counter 0
Value
Counter 0
Enable
Counter0
Underflow
0x33
0x32
0x31
0x32
0x33
0x34
………
0xF..F
0x00
Ch0_A
Ch0_B
Counter 0
Value
Counter 0
Enable
Counter0
Overflow
Содержание APAX-5013
Страница 1: ...User Manual APAX 5000 Series I O Modules...
Страница 8: ...APAX 5000 I O Series User Manual viii...
Страница 9: ...Chapter 1 1 Overview...
Страница 23: ...15 APAX 5000 I O Series User Manual Chapter 1 Overview...
Страница 33: ...Chapter 2 2 Analog Input Output Modules...
Страница 49: ...Chapter 3 3 Digital Input Output Modules...
Страница 69: ...61 APAX 5000 I O Series User Manual Chapter 3 Digital Input Output Modules APAX 5080 Function Block...
Страница 116: ...APAX 5000 I O Series User Manual 108...
Страница 117: ...Chapter 4 4 Backplane Modules...
Страница 120: ...APAX 5000 I O Series User Manual 112...
Страница 121: ...Chapter 5 5 Power Supply Modules...
Страница 124: ...APAX 5000 I O Series User Manual 116...
Страница 125: ...Chapter 6 6 Error Handling and Diagnostics...
Страница 128: ...APAX 5000 I O Series User Manual 120...