75
APAX-5000 I/O Series User Manual
Chapter 3
D
igital Input
/Output
Modules
A/B Phase 2X, With Reload, Count Once
Figure 3.17 shows A/B Phase 2X mode, Ch0_A and Ch0_B provide the counting
function. When the counter0 is enabled, the couner0 starts to count. If the counter
value is overflow or underflow, it will reset to the defined value (e.g. 0x33) and keep
counting repetitively.
Figure 3.31 A/B Phase 2X, With Reload, Count Once
0x33
0x32
0x31
0x32
0x33
0x34
………
0xF..F
0x33
Ch0_A
Ch0_B
Counter 0
Value
Counter 0
Enable
Counter0
Overflow
0x33
0x34
0x35
0x34
0x33
………
0x00
0x33
Ch0_A
Ch0_B
Counter 0
Value
Counter 0
Enable
Counter0
Underflow