Name
Set Alarm Connection
Description
Connects the High/Low alarm of the specified input channel to interlock the specified
digital output in the addressed ADAM-6000 module
Syntax $aaCjAhCCn(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadecimal Modbus network address of an
ADAM-6000/TCP module.
(Always 01)
Cj
identifies the desired analog input channel j (j : 0 to 7).
AhC
is the Set Alarm Connection command.
h
indicates alarm type (H = High alarm, L = Low alarm)
Cn
identifies the desired digital output channel n (n : 0 to 1). To disconnect the digital
output, n should be set as ‘*’.
(cr)
represents terminating character, carriage return (0Dh)
Response !aa(cr)
if the command was valid
?aa(cr)
if an invalid operation was entered.
There is no response if the system detects a syntax error or communication error
or if the specified address does not exist.
!
delimiter character indicating a valid command was received.
aa
represents the 2-character hexadecimal Modbus network address of the corresponding
ADAM-6000 module.
(cr)
represents terminating character, carriage return (0Dh)
Example
command:
$01C1ALCC0(cr)
response:
!01(cr)
Channel 1 of the ADAM-6000 module at address 01h is instructed to connect its Low alarm
to the digital output of channel 0 in the specific ADAM-6000 module.
The system confirms it has done so accordingly.
$aaCjRhC
Содержание ADAM-6000 series
Страница 21: ...Figure 3 2 Fix ADAM 6000 module on the bracket...
Страница 23: ......
Страница 24: ...Figure 3 4 Secure ADAM 6000 Module to a DIN rail...
Страница 27: ...Figure 3 6 ADAM 6000 I O Module Terminal Block wiring...
Страница 32: ...Figure 4 4 ADAM 6017 Digital Output wiring...
Страница 36: ...Figure 4 8 ADAM 6050 Digital Output Wiring...
Страница 41: ...Figure 4 13 ADAM 6051 Digital Output and Counter Wiring...
Страница 46: ...Figure 4 18 ADAM 6060 Relay Output Wiring...
Страница 75: ...Figure 5 29 Firmware Upgrade for ADAM 6000 I O Series Modules...
Страница 153: ...Appendix A Design Worksheets...