Name
Read Alarm Mode
Description
Returns the alarm mode for the specified channel in the specified ADAM-6000
module.
Syntax $aaCjAh(cr)
$
is a delimiter character.
aa
(range 00-FF) represents the 2-character hexadecimal Modbus network address of an
ADAM-6000 module. (Always 01)
Cj
identifies the desired channel j (j : 0 to 7).
A
is the Read Alarm Mode command.
h
indicates the alarm types (H = High alarm, L = Low alarm)
(cr)
represents terminating character, carriage return (0Dh)
Response !aas(cr)
if the command was valid
?aa(cr)
if an invalid operation was entered.
There is no response if the system detects a syntax error or communication error or if
the specified address does not exist.
!
delimiter character indicating a valid command was received.
aa
represents the 2-character hexadecimal address of the corresponding ADAM-6000
module.
s
indicates alarm modes (M = Momentary mode, L = Latching mode)
(cr)
represents terminating character, carriage return (0Dh)
Example
command:
$01C1AL(cr)
response:
!01M(cr)
Channel 1 of the ADAM-6000 module at address 01h is instructed to return its Low alarm
mode.
The system responds that it is in Momentary mode.
$aaCjAhEs
Содержание ADAM-6000 series
Страница 21: ...Figure 3 2 Fix ADAM 6000 module on the bracket...
Страница 23: ......
Страница 24: ...Figure 3 4 Secure ADAM 6000 Module to a DIN rail...
Страница 27: ...Figure 3 6 ADAM 6000 I O Module Terminal Block wiring...
Страница 32: ...Figure 4 4 ADAM 6017 Digital Output wiring...
Страница 36: ...Figure 4 8 ADAM 6050 Digital Output Wiring...
Страница 41: ...Figure 4 13 ADAM 6051 Digital Output and Counter Wiring...
Страница 46: ...Figure 4 18 ADAM 6060 Relay Output Wiring...
Страница 75: ...Figure 5 29 Firmware Upgrade for ADAM 6000 I O Series Modules...
Страница 153: ...Appendix A Design Worksheets...