Function Code 16 (10 hex)
Preset values into a sequence of holding registers.
Request message format for function code 16:
Command Body
Station
Address
Function
Code
Start Address
High Byte
Start Address
Low Byte
Requested Number
of Register High Byte
Requested Number
of Register Low Byte
Byte
Count
Data
Example: Preset constant #1 (address 40009) to 100.0 in ADAM-6000 module.
01 10 00 09 00 02 04 42 C8 00 00
Response message format for function code 08:
The normal responses return the station address, function code, start address, and requested number of
registers preset.
Command Body
Station
Address
Function
Code
Start Address
High Byte
Start Address
Low Byte
Requested Number
of Register High Byte
Requested Number
of Register Low Byte
Example: 01 10 00 09 00 02