Page 20
Modulating Unitary Range
VA-LT206_11292016al
Elbow and U-Bend Installation
INSTALLATION
•
If required by the heater layout, install 90° elbows or U-bend tubes where indicated. Refer to Figure 19
for details.
•
•
Note:
Elbows or U-bends are typically installed without reflectors. To reduce the above clearance to
combustibles distance use miter reflectors (see Figure 18) and refer to
Clearance to Combustibles
information.
ENDCAP
COUPLINGS
HANGER LOCATION
HANGER
LOCATION
ENDCAP
HANGER LOCATION
COUPLINGS
ELBOW DETAIL
U-BEND DETAIL
Figure 19: 90
° Elbow and U-Bend Assembly Detail
•
Elbows or U Tubes must be located not less than 10’ from the burner in VA - 80 and smaller models, not
less than 15’ from the burner in VA - 115, and not less than 20’ from the burner in VA - 150 models and
not less than 25’ from the burner in VA - 200 models.
Mitered Reflector Installation
Figure 20:
Mitered Reflector Installation
•
If used, install the Mitered Reflector as shown below (Figure 20).
ASSEMBLE CORNER BRACKET
TO MITERED REFLECTORS AS SHOWN
FASTEN MITERED REFLECTORS
WITH 4 - #8 X
3
8
" SCREWS
MITERED REFLECTOR
SECTIONS SHOULD
OVERLAP STANDARD
REFLECTORS
NOTE:
CLOSE ALL CHAIN LINKS "S" HOOKS, "J" BOLTS AND TURNBUCKLES OR ANY OPEN CONNECTION.